installation manual
8
maintenance of motor
:
4 Bolts
For fixing the fan assembly
Filter
Motor Assembly
Safety Drain Tray
12-Screw
For fixing the safety drain tray
Fig.4-17
Inside of structure
Side view of fan assembly
installation state
Front view of fan assembly installation state
Scroll
Pothook
Fan assembly should
push horizontally to the
end (about 18mm), and
then take off it.
Move 18mm
Move
The state after fan assembly is taken off
1. Refer to Fig.4-17, remove all 11
screw
from safety drain tray, and take off the safety drain tray.
3. Refer to Fig.4-17, remove all 4 bolts from fan assembly, see Fig.4-18, according to which orders to take off the fan assembly.
3. Refer to Fig.4-18, horizontal pushing the fan assembly, until it cannot not move any further, and then lift up slightly and take down to remove it.
4. After motor maintenance, reinstall the fan assemblies as per the reverse above orders. And connect the motor with electric control box, as
well as motor with power cable of capacity.
Fig.4-18
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Before dismount the fan assembly, you must remove the motor and electric control box, as well as connective wires between motor and
capacity assembly.
3. Fan subassembly is very heavy, please be careful during maintaining, otherwise physical injury would be caused.
CAUTION
Содержание KPDHF-112 DN3.0