installation manual
16
Middle fan speed
Fig.7-21
● Heating capacity and cooling capacity are tested under the
standard allowable min. static pressure; the 71 test static
pressure is 25Pa, 80/90/112 test static pressure is 37Pa,
140/160 test static pressure is 50Pa, the 200/250/280 test
pressure is 62Pa.
● The static pressure refer to Table.12-2
.
Panel installation
●
Unload inner frame.
Slide the knob, release the buckle from the outside frame hole,
then unload the inner frame.
Inside frame
Fig.7-11
●
Hang the outside frame on the main body with face down. (4
places at 4 corners).
Hang the belt on the hook of the main body.
Low fan speed
Fig.7-22
The signal wire of the remote-control receiver must be drawn out
through the canvas air passage.
●
Fix the outside frame and the canvas air passage with screws.
Screw must be fixed on from the bottom to the top.
Fig.7-14
●
Hang up the outside frame until it sticks to the ceiling tightly.
Fig.7-15
NOTE
Knob
Buckle
Outside frame
Fig.7-12
Fig.7-13
Main body
Canvas air passage
Waist-shaped hole
fixed board
Ceiling
Outside frame
Hook
Belt
Outside frame
Canvas air passage
Screw
Ceiling
Canvas air passage
Main body
Air passage
Ceiling
Outside frame