Horizontal Installation
1.1 With External pump (12K models)
Cut both ends of the rubber connective pipe into a
straight one, use it to connect the drainage outlet
and water pump and safety it with clamps on both
ends, see the figure as Shown below. (See Fig. 1)
1.3 With Built-in pump (24K, 30K, 36K, 48K, 55K
models)
Drain connector A, B & C are covered with caps
originally. Connect the drainpipe to the connector
D. (See Fig. 3)
Connector D
Connector A
Connector B Connector C
water pump port
drainage outlet
Fig. 3
clamps
Vertical Installation
rubber tubing
Fig. 1
1.2 With External pump (18K model only) Drain
connector A, B & C are covered with caps
originally. Take the cap on drain connector B off,
connect the external pump to drain connector B
using a hose & two hose clamps. Then connect
the drainpipe to the connector D. (See Fig. 2)
Plug the external pump to the “PUMP” pin and
the water level sensor to the “CN5” to enable
the pump. (See Fig.4) Fig.2
2.1 No need pump (Disable pump)
The pump must be disabled while the unit is
installed vertically or the pump assembly is
removed from its original position.
Open the cover of E-Parts Box assembly, unplug
the “PUMP” pin to disable the pump function,
and short connect ”CN5” plug to disable the
water level sensor. (See Fig. 4)
Remove the
cover
Unplug the “PUMP” pin
Short connect the “CN5”
Fig. 4
Connector A
Connector B.
Connector C
Hose Connector D
Additional Installation Guide