background image

8.5 Water system installation

Connection requirements of chilled water pipes
a) All chilled water pipelines should be thoroughly

flushed, to be free of any impurity, before the unit is

operated. Anyimpurity should not be flushed to or into

the heat exchanger.
b) Water must enter the heat exchanger through the

inlet; otherwise the performance of the unit will decline.
c) The inlet pipe of the evaporator must be provided with

a target flow controller, to realize flow-break protection

for the unit. Both ends of the target flow controller must

be supplied with horizontal straight pipe sections whose

diameter is 5 times that of the inlet pipe. The target flow

controller must be installed in strict accordance with

“Installation & Regulation Guide for Target Flow

Controller” (Fig.8-28,8-29). The wires of the target flow

controller should be led to the electric cabinet through

shielded cable (see Electric Controlling Schematic

Diagram for details). The working pressure of the target

flow controller is 1.0MPa, and its interface is 1 inch in

diameter. After the pipelines are installed, the target flow

controller will be set properly according to the rated

water flow of the unit.
d) The pump installed in the water pipeline system

should be equipped with starter. The pump will directly

press water into the heat exchanger of the water system.
e) The pipes and their ports must be independently

supported but should not be supported on the unit.
f) The pipes and their ports of the heat exchanger should 

be easy to disassemble for operation and cleaning, as

well as inspection of port pipes of the evaporator.

g) The evaporator should be provided with a filter with

more than 40 meshes per inch at site. The filter should

be installed near to the inlet port as much as possible,

and beunder heat preservation.
h) The by-pass pipes and by-pass valves as shown in

Fig.8-23 must be mounted for the heat exchanger, to

facilitate cleaning of the outside system of water

passage before the unit is adjusted. During

maintenance, the water passage of the heat exchanger

can be cut off without disturbing other heat exchangers.
i) The flexible ports should be adopted between the

interface of the heat exchanger and on-site pipeline, to

reduce transfer of vibration to the building.
j) To facilitate maintenance, the inlet and outlet pipes

should be provided with thermometer or manometer.

The unit is not equipped with pressure and temperature

instruments, so they need to be purchased by the user.
k) All low positions of the water system should be

providedwith drainage ports, to drain water in the

evaporator and the system completely; and all high

positions should be supplied with discharge valves, to

facilitate expelling air from the pipeline. The discharge

valves and drainage ports should not be under heat

preservation, to facilitate maintenance.
l) All possible water pipes in the system to be chilled

should be under heat preservation, including inlet pipes

and flanges of the heat exchanger.
m) The outdoor chilled water pipelines should be

wrapped with an auxiliary heating belt for heat

preservation, and the material of the auxiliary heat belt

should be PE, EDPM, etc., with thickness of 20mm, to

prevent the pipelines from freezing and thus cracking

under low temperature. The power supply of the heating

belt should be equipped with an independent fuse.
n) The temperature sensor of the total outlet water of No. 

0 master unit needs to be installed in the main outlet

water pipe of the project.

After the unit is in place, chilled water pipes 

can be laid.
The relevant installation regulations should 

be abided with when conducting connection 

of water pipes.
The pipelines should be free of any impurity, 

and all chilled water pipes must conform to 

local rules and regulations of pipeline 

engineering.

CAUTION

8.5.1 Basic requirements of connection

        of chilled water pipes

NOTE

When the power cord is parallel to the signal wire, 

make sure that they are enclosed in respective 

conduits and are kept a reasonable wire spacing. 

(Distance between the power cord and signal wire: 

300mm if below 10A, and 500mm if below 50A)

WARNING

For the water pipeline network including 

filters and heat exchangers, dreg or dirt may 

seriously damages the heat exchangers and 

water pipes.
The installation persons or the users must 

ensure the quality of chilled water, and 

de-icing salt mixtures and air should be 

excluded from the water system, since they 

may oxidize and corrode steel parts inside 

the heat exchanger.

When the ambient temperature is lower than 

2

, and the unit will be not used for a long 

time, water inside the unit should be drained. 

If the unit is not drained in winter, its power 

supply should not be cut off, and the fan coils 

in the water system must be provided with 

three-way valves, to ensure smooth 

circulation of the water system when the 

anti-freezing pump is started up in winter.

For 

KEM-180  DRS5  KH

,  the  temperature 

sensor  of  the  total  outlet  water  of 

the  master  unit  module  A  (the  uint 

address  of DIP switches is 0) must be 

repositioned on the water outlet main of 

the project.

30

Содержание KEM-75 DRS5 KH

Страница 1: ...our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference OWNER S INSTALLATION MANUAL DC Inverter Air cooled Modular Chiller KEM 75 DRS5...

Страница 2: ...trong breeze 6 1 6 2 6 3 6 4 6 5 PRECAUTIONS ON INSTALLATION 11 7 CONNECTION DRAWING OF PIPELINE SYSTEM 13 11 8 15 20 30 Main parts of the uint Opening the uint Outdoor unit PCBs Electric wiring Water...

Страница 3: ...1 5 11 6 11 7 11 8 11 9 11 10 11 11 11 12 11 13 36 38 38 38 38 39 39 39 39 44 40 41 44 39 38 Failure information and code Data display of wired controller Care and maintenance Removing scale Winter sh...

Страница 4: ...n above 15 should be added in the water system otherwise the unit and the water system will be damaged Outlet water temperature Outlet water temperature G KEM 75 DRS5 KH KEM 140 DRS5 KH KEM 75 DRS5 KH...

Страница 5: ...used to alert against unsafe practices Indicates situations that could only result in accidental equipment or property damage NOTE Explanation of symbols displayed on the indoor unit or outdoor unit...

Страница 6: ...tidy the wires so that the front panel can be securely fastened If the front panel is not in place there could be overheating of the terminals electric shocks or fire After completing the installation...

Страница 7: ...Children should not play with the unit Cleaning and user maintenance should not be done by children without supervision This appliance is intended to be operated by expert or trained users in shops i...

Страница 8: ...can be fastened on the foundation reliability 7 If the unit is installed on a roof the roof must be strong enough to bear the weight of the unit and the weight of maintenance personnel The unit can b...

Страница 9: ...6 PRECAUTIONS ON INSTALLATION 6 1 Outline dimensional drawing Fig 6 1 Outline dimensional 06 Front view Left view Top view...

Страница 10: ...will increase by 135mm approximately Model A B C D E F KEM 90 DRS5 KH 2220 1135 2315 910 255 270 Table 6 1 KEM 75 DRS5 KH 2000 960 1770 816 190 270 KEM 140 DRS5 KH 2220 1135 2300 910 185 380 KEM 180...

Страница 11: ...ss than the static pressure outside the fan The space between the unit and sunk fence or Persian blinds should also meet the requirement 3 If the unit needs to operate in winter and the installation s...

Страница 12: ...ructed on solid ground or on structures of sufficient strength to support the units weight 2 Bases should be at least 200mm high to provide sufficient access for installation of piping Snow protection...

Страница 13: ...sure trouble free operation of the equipment Otherwise accumulated snow will block the air flow and may cause equipment problems Check the installation site thoroughly do not install the equipment und...

Страница 14: ...AME Air inlet Water outlet wire controller It can be placed indoors Expansion tank Gas liquid separator Induction pump Table 8 1 Stop valve Pressure gauge Water flow switch Gate valve Flexible joint Y...

Страница 15: ...M 90 DRS5 KH Picture just use to show the key component relative position Fig 8 3 Main parts of KEM 140 DRS5 KH Picture just use to show the key component relative position Fig 8 4 Main parts of KEM 1...

Страница 16: ...nger Cover 4 give access to the electrical parts Cover 5 6 give access to the hydraulic compartment Cover 1 Cover 2 Cover 3 Cover 6 Cover 5 Cover 4 Fig 8 7 Doors of KEM 90 DRS5 KH KEM 140 DRS5 KH Cove...

Страница 17: ...2 Door 3 Door 4 Door 5 Door 6 Door 7 Door 8 Door 9 Door 10 Door 1 2 3 9 10 give access to the compartment of water pipes and water side heat exchanger Door 4 5 give access to the hydraulic compartment...

Страница 18: ...rt value of the alarm actually detected is ON OFF but not 220 240V control power supply so special attention should be paid when installing the alarm signal output CN68 Pump 220 240V control power sup...

Страница 19: ...enser CN30 T4 outdoor ambient temperature sensor CN45 Taf2 Water side antifreeze temperature sensor CN16 T3B pipe temperature sensor of the condenser CN38 Tp2 DC inverter compressor B discharge temper...

Страница 20: ...ate of the compressor Attention the control port value of the COMP STATE actually detected is ON OFF but not 220 240V control power supply so special attention should be paid when installing the light...

Страница 21: ...solenoid valve CN80 Injection solenoid valve of compressor system B CN47 Injection solenoid valve of compressor system A CN5 Water side heat exchanger heaters connection CN40 Multi function solenoid...

Страница 22: ...essor inverter module communication ports CN300 Program burn in port WizPro200RS programming device IC10 EEPROM chip CN1 temperature sensors input port T4 outdoor ambient temperature sensor T3A T3B pi...

Страница 23: ...power supply whose voltage should conform to rated voltage Wiring construction must be conducted by the professional technicians according to the labeling on the circuit diagram The power wire and the...

Страница 24: ...2 1 DSP1 DSP2 8 4 2 KEM 75 DRS5 KH and KEM 140 DRS5 KH DIP switch buttons and digital display positions of uints Fig 8 13 Display positions 8 4 2 KEM 90 DRS5 KH and KEM 180 DRS5 KH DIP switch buttons...

Страница 25: ...cal standards b Copper core wires must be used Fig 8 15 1 Electrical wiring precaution a Fig 8 15 2 Electrical wiring precaution b c It is advisable to use 3 core shielded cables for uint to minimize...

Страница 26: ...arrester Power distribution transformer Wrong Manual switch Fuses Power 380 415V 3N 50Hz Fig 8 16 Requirements of power supply wiring Uint NOTE Do not connect the grounding wire of the lightning arres...

Страница 27: ...S5 KH 0 electric control box ON OFF port ON Power DC 12V Main control board is provided 0 electric control box ON OFF port OFF Power DC 12V Main control board is provided Fig 8 21 1 Wiring of ON OFF w...

Страница 28: ...ll cause the units to malfunction b The shielding nets at both ends of the shielded wire must be grounded Alternatively the shielding nets of all shielded wires are interconnected and then connected t...

Страница 29: ...the actual parameter of products and national Contactor Contactor Power Transformer OUTPUT 8 5 V Contactor MAIN CONTROL WIRECONTROLLER X Y X Y X Y XT3 L1 L 2 L3 POWER 380 415V 3N 50Hz ENC1 AC1 AC2 MAI...

Страница 30: ...AC2 RD YE BK BR WH MONITOR WIRECONTROLLER CN60 5 6 7 8 9 10 11 12 5 6 7 8 9 10 11 12 CN74 CN61 WH RD YE BK BR RD YE BK BR WH MONITOR WIRECONTROLLER X Y X Y X Y X Y E X Y E CN25 XT3 CN30 XT3 CN2 CN83 C...

Страница 31: ...ing to the actual parameter of products and national Contactor Contactor Power Transformer OUTPUT 8 5 V MAIN CONTROL WIRECONTROLLER X Y X Y X Y Contactor XT3 POWER 380 415V 3N 50Hz POWER 380 415V 3N 5...

Страница 32: ...1 F indicate slave units 29 Fig 8 28 Networking communication schematic of main unit and auxiliary unit for KEM 180 DRS5 KH Contactor Contactor for pipeline Contactor for water tank 7 MONITOR WIRECON...

Страница 33: ...so they need to be purchased by the user k All low positions of the water system should be providedwith drainage ports to drain water in the evaporator and the system completely and all high position...

Страница 34: ...S5 KH model uses hoop connection For the specifications of the water pipes and screw thread see the Table 8 5 below Table 8 5 kW is the unit for cooling capacity and L is the unit for G water flow in...

Страница 35: ...rated water flow in terms of multi connect the units that water flow must no less than total units rated water flow b Select the left of the pump H h1 h2 h3 h4 H The lift of the pump h1 Main unit wate...

Страница 36: ...ine 2 Table of diameter parameters of main inlet and outlet pipes 2 Applicable standard of water quality for the unit PH value Total hardness Conductivity Sulfide ion Chloride ion Ammonia ion Sulfate...

Страница 37: ...er outlet temperature sensing bulb target flow controller and auxiliary electric heater are under control of the main module One wired controller and one target flow controller are required and connec...

Страница 38: ...ent Wire capacity is meeting for requirement Switch capacity is meeting for requirement Fuse capacity is meeting for requirement Voltage and frequency are meeting for requirement Connecting tightly be...

Страница 39: ...on for 3 times in 60 minutes Recovered by power off 1P0 Compressor module 1 high pressure protection Recovered upon failure recovery 2P0 Compressor module 2 high pressure protection Recovered upon fai...

Страница 40: ...A 2 for Compressor B Recovered upon error recovery 53 xL7 phase loss x 1or 2 1 for Compressor A 2 for Compressor B Recovered upon error recovery 54 xL8 frequency change over 15Hz x 1or 2 1 for Compre...

Страница 41: ...be made on the set points on site Regularly check whether the electric connection is loose and whether there is bad contact at the contact point caused by oxidation and debris etc and take timely mea...

Страница 42: ...nt of refrigerant will be affected by the ambient temperature If the required amount has not been reached but no more injection can be done make the chilled water circulate and start up the unit for i...

Страница 43: ...afety valve safety valve liquid vapor separator The air outlet of safty valve must be connected to the appropriate pipe which can direct the leaking refrigerant to the appropriate place for discharge...

Страница 44: ...the period that the work is carried out The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere 8 Checks to the refrigeration equipment W...

Страница 45: ...be repeated until no refrigerant is within the system When the final OFN charge is used the system shall be vented down to atmospheric pressure to enable work to take place This operation is absolutel...

Страница 46: ...gerants are removed safely When tranferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct numbers of cylinders for holding...

Страница 47: ...C C MPa MPa V A C C C C A High pressure Low pressure Voltage Current Inlet dry bulb Outlet dry bulb Inlet Outlet 1 Check temperature of chilled water or hot water Inlet Outlet 2 Check air temperature...

Страница 48: ...unit Net Weight Operation Weight Packing dimension Type Chargeing volume kg Waterflow volume m 3 h cooling Hydraulic resistance lose kPa Water side heat exchanger Max pressure MPa Min pressure MPa Inl...

Страница 49: ...ne or water flow rate outdoor side heat exchanger Sound power level indoors outdoors Emissions of nitrogen oxides if applicable GWP of the refrigerant Standard rating conditions used Contact details I...

Страница 50: ...ow rate outdoor side heat exchanger Sound power level indoors outdoors Emissions of nitrogen oxides if applicable GWP of the refrigerant Standard rating conditions used Contact details If Cdc is not d...

Страница 51: ...ow rate outdoor side heat exchanger Sound power level indoors outdoors Emissions of nitrogen oxides if applicable GWP of the refrigerant Standard rating conditions used Contact details If Cdc is not d...

Страница 52: ...outdoor side heat exchanger Sound power level indoors outdoors Emissions of nitrogen oxides if applicable GWP of the refrigerant Standard rating conditions used Contact details If Cdc is not determine...

Страница 53: ...tandby mode Crankcase heater mode Capacity control Fixed Variable Variable Sound power level indoors Sound power level outdoors Contact details 1 For heat pump space heaters and heat pump combination...

Страница 54: ...andby mode Crankcase heater mode Capacity control Fixed Variable Variable Sound power level indoors Sound power level outdoors Contact details 1 For heat pump space heaters and heat pump combination h...

Страница 55: ...e Standby mode Crankcase heater mode Capacity control Fixed Variable Variable Sound power level indoors Sound power level outdoors Contact details 1 For heat pump space heaters and heat pump combinati...

Страница 56: ...de Standby mode Crankcase heater mode Capacity control Fixed Variable Variable Sound power level indoors Sound power level outdoors Contact details 1 For heat pump space heaters and heat pump combinat...

Страница 57: ......

Страница 58: ......

Страница 59: ...16127100A09250 V D...

Страница 60: ......

Отзывы: