Fig. 8-30 Connection mode of KEM-90 DNS3 pipe
8.6.3 Design of the store tank in the system
kW is the unit for cooling capacity and L is the unit for G, water flow in the formula counting the minimum water flow.
Comfortable air conditioner
G = cooling capacity×3.5L
Process cooling
G = cooling capacity×7.4L
In certain occasion (especially in manufacture cooling process), for conforming the system water content requirement, it’s necessary to mount
a tank equipping with a cut-off baffle at the system to avoid water short-circuit, Please see the following schemes:
Error
Recommendation
Error
Recommendation
Fig. 8-31 Design of the store tank