32
Port provide the control signal to the load.Two kind of control signal
port:
Type 1
:
Dry connector without voltage.
Type 2
:
Port provide the signal with 220V voltage. If the current of
load is <0.2A, load can connect to the port directly.
If the current of load is >=0.2A, the AC contactor is required to
connected for the load.
Unit 5-16kW
9.6.6 Connection for other components
See 9.2.1for detailed port description.
CN11
Load
L N
FUSE
Type 1
Type 2
ATCO
TCO
A2
7 5 3 1 A1
8 6 4 2
Power supply
Contactor
Load
CN11
Control signal port of hydraulic module: The CN11contains
terminals for 3-way valve, pump,booster heater , etc.
The parts wiring is illustrated below:
This part only applies to Basic. For Customized, cause there
is an interval backup heater in the unit, the hydraulic module
should not be connected to any additional heat source.
WARNING
1) For additional heat source control(AHS)
:
KM1
FUSE
Power supply
7 5 3 1 A1
A2
2
4
6
8
L
N
Additional heat source
Control port signal type
Voltage
Maximum running current(A)
Wiring size(mm
2
)
Type 2
220-240VAC
0.2
0.75
Load
L N
FUSE
1 2
CN11
AHS1 AHS2
1 2
CN11
AHS1 AHS2
Control port signal type
Voltage
Maximum running current(A)
Wiring size(mm
2
)
Type 2
220-240VAC
0.2
0.75