7.3 Drain hole position
Drain hole
7.1 Dimensions
7 INSTALLATION PRECAUTIONS
Model
A
B
C
D
E
F
G
H
I
J
5-16kW
1040
410
458
523
191
656
64
865
165
279
Check the strength and level of the installation ground so that the unit may not cause any vibrations or noise during its
operation.
In accordance with the foundation drawing in the figure, fix the unit securely by means of foundation bolts. (Prepare four sets
each of
Φ
10 Expansion bolts, nuts and washers which are readily available in the market.)
Screw in the foundation bolts until their length is 20 mm from the foundation surface.
7.2 Installation requirements
(unit: mm)
Concrete
basement
h
≥
100mm
Rubber
shocking
proof mat
≥
100
≥
80
Φ
10 Expansion
bolt
Solid
ground
or roofing
This drain hole is
covered by rubber
plug. If the small
drain hole can not
meet the drainage
requirements, the
big drain hole can
be used at the
same time.
K
89
09
A
B
C
D
E
F
G
I
J
K
H
(unit:mm)