29
Voltage
(V)
Hz
Min.
(V)
Max.
(V)
MCA
(A)
TOCA
(A)
MFA
(A)
MSC
(A)
RLA
(A)
KW
FLA
(A)
Outdoor Unit
Power Current
Compressor
OFM
1
1
1
1
14.5
18
-
10.50
0.17
1.50
264
25
220-240 50
198
-
10.50
0.17
1.50
16
18
264
25
220-240 50
198
13
25
-
0.17
1.50
220-240 50
198
264
18
10.50
System
7kW
5kW
9kW
-
25
30
17.00
0.17
1.50
264
198
40
220-240 50
12kW 1-PH
-
26.5
30
17.00
0.17
1.50
264
198
40
220-240 50
14kW 1-PH
1
-
28
30
17.00
0.17
1.50
264
198
40
220-240 50
16kW 1-PH
-
9.5
14
16.00
0.17
0.70
456
342
16
380-415 50
12kW 3-PH
1
-
10.5
14
16.00
0.17
0.70
456
342
16
380-415 50
14kW 3-PH
-
11.5
14
16.00
0.17
0.70
456
342
16
380-415 50
16kW 3-PH
Table 9-2
Rated current
of appliance:
(
A
)
Nominal cross-sectional area (mm )
2
Flexible cords
Cable for fixed wiring
Table 9-1
≤
3
0.5 and 0.75
1 and 2.5
>
3 and
≤
6
0.75 and 1
1 and 2.5
>
6 and
≤
10
1 and 1.5
1 and 2.5
>
10 and
≤
16
1.5 and 2.5
1.5 and 4
>
16 and
≤
25
2.5 and 4
2.5 and 6
>
25 and
≤
32
4 and 6
4 and 10
>
32 and
≤
50
6 and 10
6 and 16
>
50 and
≤
63
10 and 16
10 and 25
1-phase 5-16kW standard and 3-phase 12-16kW standard
9.6.5 Remove the switch box cover
NOTE
Unit
5kW
7kW
9kW
12kW
14kW
16kW 12kW 3-PH 14kW 3-PH 16kW 3-PH
Maximum
overcurrent
protector(MOP)(A)
18
18
18
30
30
30
14
14
14
Wiring size(mm
2
)
4.0
4.0
4.0
6.0
6.0
6.0
2.5
2.5
2.5
MCA : Minimum. Circuit Amps. (A)
TOCA : Total Over-current Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. Starting Amps. (A)
RLA : In nominal cooling or heating test condition
,
the input Amps of compressor where MAX. Hz
can operate Rated Load Amps. (A)
KW : Rated Motor Output
FLA : Full Load Amps. (A)
1-phase 5-16kW standard and 3-phase 12-16kW standard
UNIT POWER SUPPLY
1-phase
L
N
L N
LPS
F
USE
UNIT POWER SUPPLY
3-phase
LPS
F
USE
L1
N
L2 L3
L3
N
L2
L1
The ground fault circuit interrupter must be 1 high-speed type of 30mA(<0.1s). Please use 3-core shielded wire.
Stated values are maximum values (see electrical data for exact values).
Leakage protection switch must be installed to the power supply of the unit.