Appendix

 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4,T2B (

--K) 

 

K Ohm 

 

K Ohm 

 

K Ohm 

 

K Ohm 

-20 

115.266 

20 

12.6431 

60 

2.35774 

100 

0.62973 

-19 

108.146 

21 

12.0561 

61 

2.27249 

101 

0.61148 

-18 

101.517 

22 

11.5000 

62 

2.19073 

102 

0.59386 

-17 

96.3423 

23 

10.9731 

63 

2.11241 

103 

0.57683 

-16 

89.5865 

24 

10.4736 

64 

2.03732 

104 

0.56038 

-15 

84.2190 

25 

10.000 

65 

1.96532 

105 

0.54448 

-14 

79.3110 

26 

9.55074 

66 

1.89627 

106 

0.52912 

-13 

74.5360 

27 

9.12445 

67 

1.83003 

107 

0.51426 

-12 

70.1698 

28 

8.71983 

68 

1.76647 

108 

0.49989 

-11 

66.0898 

29 

8.33566 

69 

1.70547 

109 

0.48600 

-10 

62.2756 

30 

7.97078 

70 

1.64691 

110 

0.47256 

-9 

58.7079 

31 

7.62411 

71 

1.59068 

111 

0.45957 

-8 

56.3694 

32 

7.29464 

72 

1.53668 

112 

0.44699 

-7 

52.2438 

33 

6.98142 

73 

1.48481 

113 

0.43482 

-6 

49.3161 

34 

6.68355 

74 

1.43498 

114 

0.42304 

-5 

46.5725 

35 

6.40021 

75 

1.38703 

115 

0.41164 

-4 

44.0000 

36 

6.13059 

76 

1.34105 

116 

0.40060 

-3 

41.5878 

37 

5.87359 

77 

1.29078 

117 

0.38991 

-2 

39.8239 

38 

5.62961 

78 

1.25423 

118 

0.37956 

-1 

37.1988 

39 

5.39689 

79 

1.21330 

119 

0.36954 

35.2024 

40 

5.17519 

80 

1.17393 

120 

0.35982 

33.3269 

41 

4.96392 

81 

1.13604 

121 

0.35042 

31.5635 

42 

4.76253 

82 

1.09958 

122 

0.3413 

29.9058 

43 

4.57050 

83 

1.06448 

123 

0.33246 

28.3459 

44 

4.38736 

84 

1.03069 

124 

0.32390 

26.8778 

45 

4.21263 

85 

0.99815 

125 

0.31559 

25.4954 

46 

4.04589 

86 

0.96681 

126 

0.30754 

24.1932 

47 

3.88673 

87 

0.93662 

127 

0.29974 

22.5662 

48 

3.73476 

88 

0.90753 

128 

0.29216 

21.8094 

49 

3.58962 

89 

0.87950 

129 

0.28482 

10 

20.7184 

50 

3.45097 

90 

0.85248 

130 

0.27770 

11 

19.6891 

51 

3.31847 

91 

0.82643 

131 

0.27078 

12 

18.7177 

52 

3.19183 

92 

0.80132 

132 

0.26408 

13 

17.8005 

53 

3.07075 

93 

0.77709 

133 

0.25757 

14 

16.9341 

54 

2.95896 

94 

0.75373 

134 

0.25125 

15 

16.1156 

55 

2.84421 

95 

0.73119 

135 

0.24512 

16 

15.3418 

56 

2.73823 

96 

0.70944 

136 

0.23916 

17 

14.6181 

57 

2.63682 

97 

0.68844 

137 

0.23338 

18 

13.9180 

58 

2.53973 

98 

0.66818 

138 

0.22776 

19 

13.2631 

59 

2.44677 

99 

0.64862 

139 

0.22231 

 

Содержание KAM2-42 DN5

Страница 1: ...SERVICE MANUAL AIRCONDITIONER DC INVERTER MULTI TYPE KAM2 42 DN5 KAM2 52 DN5 KAM3 62 DN5 KAM3 80 DN5 KAM4 72 DN KAM4 80 DN5 KAM4 105 DN5 KAM5 105 DN5 KAM5 120 DN5 DC MULTI OUTDOOR UNITS...

Страница 2: ...information of Outdoor Units 2 2 Features 3 3 Dimensions 4 4 Wiring Diagram 10 5 Refrigeration Cycle Diagram 13 6 Indoor units combination 16 7 Installation Details 19 8 Electronic control function 29...

Страница 3: ...sor KAM2 42 DN5 845x320x700 DA130M1C 31FZ KAM2 52 DN5 845x320x700 DA150S1C 20FZ KAM3 62 DN5 845x320x700 DA150S1C 20FZ KAM3 80 DN5 900x315x860 DA250S2C 30MT KAM4 105 DN5 990x345x965 TNB306FPGMC L KAM5...

Страница 4: ...valves and prevents water from dripping 4 way valve control It is only operated in the heating operation mode except defrosting operation Outdoor unit Power relay control Hydrophilic aluminum fin Ant...

Страница 5: ...4 3 Dimensions KAM2 42 DN5 KAM2 52 DN5 560 W1 H 6 D1 335 D2 360 845 W 313 D3 335 D1 R6 R5 A1 22 A2 50 B1 120 110 B2 700 W2 73 58 58 58 110 H1 H2 200 7 243 6 L1 L2...

Страница 6: ...5 KAM3 62 DN5 560 W1 H 6 D1 335 D2 360 845 W 313 D3 335 D1 R6 R5 A1 22 A2 50 B1 120 110 B2 700 W2 73 58 58 58 58 58 110 H1 H2 200 7 243 6 L1 L2...

Страница 7: ...6 KAM3 80 DN5 900 W 590 W1 860 H 12 D2 355 D1 333 302 D3 333 D1 50 97 90 B2 B1 8 A2 55 55 55 55 55 110 62 W2 H1 H2 R6 238 4 285 7 L1 L2...

Страница 8: ...7 KAM4 80 DN5 900 W 590 W1 860 H 12 D2 355 D1 333 302 D3 333 D1 50 97 90 B2 B1 8 A2 55 55 55 55 55 55 55 110 62 W2 H1 H2 R6 238 4 285 7 L1 L2...

Страница 9: ...8 KAM4 105 DN5 624 W1 990 W D2 397 D1 366 965 10 H 78 W2 340 366 D3 D1 125 145 B1 B2 60 22 A2 A1 55 140 H1 H2 R5 R6...

Страница 10: ...9 KAM5 105 DN5 KAM5 120 DN5 990 W W2 81 624 W1 D2 397 D1 366 55 H1 965 H 153 H2 366 D1 B2 125 B1 145 D3 345 60 22 A2 A1 R5 R6...

Страница 11: ...10 4 Wiring Diagram KAM2 42 DN5 KAM2 52 DN5...

Страница 12: ...11 KAM3 80 DN5 KAM3 62 DN5 KAM4 80 DN5...

Страница 13: ...12 KAM4 105 DN5 KAM5 105 DN5 KAM5 120 DN5...

Страница 14: ...PILIARY B LIQUID VALVE B GAS VALVE B Accumulator T2B A Evaporator temp sensor outlet T2B B 5 2 Refrigeration circuit drawing of inverter 1 drive 3 type LIQUID VALVE A GAS VALVE A HEAT EXCHANGE EVAPORA...

Страница 15: ...switch Low pressure switch T2B A Evaporator temp sensor outlet T2B B T2B C T2B D 5 4 Refrigeration circuit drawing of KAM5 105 DN5 LIQUID VALVE A GAS VALVE A HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CO...

Страница 16: ...T3 Condenser temp sensor T4 Ambient temp sensor INDOOR OUTDOOR EXV A CAPILIARY A CHECK VALVE CAPILIARY TUBE EXV B CAPILIARY B LIQUID VALVE B GAS VALVE B EXV C CAPILIARY C LIQUID VALVE C GAS VALVE C E...

Страница 17: ...18 7 18 12 12 6 3 Indoor unit combination for KAM3 62 DN5 One unit Two unit Three unit 7 7 7 9 9 7 7 7 7 9 12 9 7 9 9 12 7 7 9 9 9 9 12 7 12 9 18 7 7 12 9 9 12 18 7 18 12 12 7 9 9 6 4 Indoor unit comb...

Страница 18: ...2 18 9 9 12 18 Five Unit One unit Two unit Three unit Four unit 7 7 7 9 9 12 18 7 7 7 7 9 9 9 9 9 7 7 7 7 7 7 9 9 7 9 9 12 7 7 7 7 9 7 9 9 12 18 18 7 7 9 7 9 12 9 9 12 7 7 7 9 7 7 9 12 7 9 12 12 7 7 7...

Страница 19: ...7 7 7 12 18 7 7 12 12 18 7 9 12 12 12 9 9 9 12 18 7 7 7 7 12 7 7 7 18 18 7 9 9 9 9 7 9 12 12 18 9 9 12 12 12 7 7 7 7 18 7 7 9 9 9 7 9 9 9 12 9 9 9 9 9 9 12 12 12 12 7 7 7 9 9 7 7 9 9 12 7 9 9 9 18 9...

Страница 20: ...current indicated on the nameplate which located on the side panel of the unit Please refer to the nameplate before selecting the cable fuse and switch 7 3 Pipe length and the elevation Maximum pipin...

Страница 21: ...9 52 3 8 7 4 Installation for the first time Air and moisture in the refrigerant system have undesirable effects as below Pressure in the system rises Operating current rises Cooling or heating effici...

Страница 22: ...lease check if there are some leakage points Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump Confirm that the gauge needle does not move approximately 5...

Страница 23: ...te repeat 3 times After purging the air use a torque wrench to tighten the flare nut on the 2 way valve 4 Check the gas leakage Check the flare connections for gas leakage 5 Discharge the refrigerant...

Страница 24: ...bottom of the cylinder and press the check valve on the charge set to purge the air be careful of the liquid refrigerant 3 Put the charging cylinder onto the electronic scale and record the weight 4 O...

Страница 25: ...inder onto the electronic scale and record the weight 4 Operate the air conditioner at the cooling mode 5 Open the valves Low side on the charge set and charge the system with liquid refrigerant 6 Whe...

Страница 26: ...he manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly 4 Set the 2 way valve to the close position 5 Operate the air conditioner at the cooling cycle and...

Страница 27: ...or 1 minute repeat 3 times After purging the air use a torque wrench to tighten the flare nut on the 2 way valve 4 Check the gas leakage Check the flare connections for gas leakage 5 Discharge the ref...

Страница 28: ...at both the 2 way and 3 way valves are set to the opened position 2 Connect the vacuum pump to 3 way valve s service port 3 Evacuation for approximately one hour Confirm that the compound meter indica...

Страница 29: ...ow side on the charge set and charge the system with liquid refrigerant If the system cannot be charge with the specified amount of refrigerant or can be charged with a little at a time approximately...

Страница 30: ...the LED displays In compressor operation the LED display the running frequency In defrosting mode The LED displays dF or alternative displays between running frequency and dF each displays 0 5s In com...

Страница 31: ...r unit evaporator outlet temp T2BA If the temp is lower than 9 degree the digital display tube will show 9 If the temp is higher than 70 degree the digital display tube will show 70 If the indoor unit...

Страница 32: ...rrent Bit6 Frequency limit caused by PFC Bit5 Frequency limit caused by T4 Bit4 Frequency limit caused by T2 Bit3 Frequency limit caused by T3 Bit2 Frequency limit caused by T5 Bit1 Frequency limit ca...

Страница 33: ...s 4 0 a 3 1 1 3 1 2 0 b c d e f 2 Capacity area a b c d e f Norm value N 3 2 1 5 1 0 5 0 8 4 4 Number of indoor unit Display Number of indoor unit 1 1 2 2 3 3 4 4 5 5 8 4 5 Opening degree of electroni...

Страница 34: ...s the compressor frequency will be limited as below table Cooling mode Current frequency Hz Current limit value A Frequency limit COOL_F16 ICOOLLMT12 Decrease the frequency to COOL_F4 and run at COOL_...

Страница 35: ...6 High condenser coil temp protection When T3 65 for 3 seconds the compressor will stop while the indoor fan and outdoor fan will continue When T3 52 the protection will release and the compressor wi...

Страница 36: ...on P5 6 Mode conflict P6 7 Low pressure protection Just matching with KAM4 105 DN5 KAM4 80 DN5 KAM5 105 DN5 KAM5 120 DN5 O light X off flash Other series Except Console NO MALFUNCTION RUN Timer DEF Al...

Страница 37: ...ween indoor and outdoor units X X 4 Outdoor fan speed has been out of control X O 5 Indoor EEPROM malfunction X 6 IPM module protection X 7 Open or short circuit of T3 or T4 temperature sensor or Outd...

Страница 38: ...F3 No C Indoor unit coil outlet temperature sensor or connector of sensor is defective F4 No D Indoor unit coil outlet temperature sensor or connector of sensor is defective F5 No E Indoor unit coil o...

Страница 39: ...tion If the EEPROM chip is welded on PCB replace the PCB directly Otherwise check whether the EEPROM chip plugged in PCB well Yes No Yes Insert the EEPROM well Replace the indoor PCB Shut off the powe...

Страница 40: ...n on all indoor unit by remote controller Is all indoor unit display Turn off the all indoor units Is IPM power LED or operating LED lamp On Refer PIC2 Yes A Is all the wiring between terminal and Ind...

Страница 41: ...2 IPM For dual tri zone Self Check Power Operating Self Check Operating els Pic 2 IPM For qua zone Pic 1 check the voltage of N to S Vs is it moving alternately between positive value and negative va...

Страница 42: ...PIC3 Main board LED when power on and unit standby PIC 4 check point button Press 1 time for check how many indoor units are connected...

Страница 43: ...tions No Yes Check whether the main PCB is normal through index 2 Yes Yes Check whether the fan motor is normal through index 1 Yes Replace the fan motor Replace the main PCB The malfunction is solved...

Страница 44: ...5 Yellow 6 Black Index2 1 Indoor AC fan motor Power on and set the unit running in fan mode at high fan speed After running for 15 seconds measure the voltage of pin1 and pin2 If the value of the vol...

Страница 45: ...tor connector If the value of the voltage is not in the range showing in below table the PCB must have problems and need to be replaced For other models For console 5 4 6 3 2 1 DC motor voltage input...

Страница 46: ...or Signal Voltage 1 Red Vs Vm 192V 380V 2 3 Black GND 0V 4 White Vcc 13 5 16 5V 5 Yellow Vsp 0 6 5V 6 Blue FG 15V For console 5 4 6 3 2 1 NO Color Signal Voltage 1 Red VDC 310V 2 3 White Vcc 15V 4 Blu...

Страница 47: ...or PCB Replace the sensor Check the resistance value of the sensor via Appendix 1 Is it normal No 9 3 1 6 Full water malfunction If the water level switch is inserted well No Insert the water level sw...

Страница 48: ...r EEPROM malfunction ODU E0 If the EEPROM chip is welded on PCB replace the PCB directly Otherwise check whether the EEPROM chip plugged in PCB well Yes No Yes Insert the EEPROM well Replace the outdo...

Страница 49: ...he IPM board light Check the signal wire between the IPM module and the main board is it connected good Reconnect and retry Is error still display Replace IPM board and then check whether the system c...

Страница 50: ...0VAC Check the power supply Check whether the voltage of IPM board P and N is normal DC277 356V for 18 27KBtu h DC277 410V for 36 42KBtu h Replace bridge rectifiers and then check whether the system c...

Страница 51: ...the wires of fan motor Are all the connections good No Yes No Correct the connections No Yes Check whether the main PCB is normal through index 2 Yes Yes Check whether the fan motor is normal through...

Страница 52: ...sure the voltage of pin1 pin3 pin4 pin3 in fan motor connector If the value of the voltage is not in the range showing in below table the PCB must have problems and need to be replaced For other model...

Страница 53: ...ce high pressure protector Yes Judge 2 Whether the high pressure protector is broken Check whether the refrigerant system is ok Judge 3 Check whether the outdoor ambient temperature is higher than 50...

Страница 54: ...stem is ok Judge 3 Check whether the outdoor ambient temperature is too low No Stop the unit Yes Method Connect the pressure gauge to the gauge joint of the system check whether the pressure is lower...

Страница 55: ...or unit ventilate well Yes Judge 5 The refrigerant pipe is blocked No Let the refrigerant out then use the high pressure nitrogen or refrigerant to blow pipe vacuumize and charge the refrigerant again...

Страница 56: ...d PCB according to wiring diagrams Method Check whether the resistance of compressor discharge temp sensor is right refer to the Appendix 2 No Yes Yes Trouble is solved No Judge The discharge temp sen...

Страница 57: ...ck whether the outdoor ambient temperature is higher than 50 No Judge 3 The refrigerant pipe is blocked Let the refrigerant out then use the high pressure nitrogen or refrigerant to blow pipe vacuumiz...

Страница 58: ...the compressor check whether the system can work normally Check whether the lines in E part box are connected tightly Yes Connect it tightly check ok or not No No Yes No Replace the bridge rectifiers...

Страница 59: ...motor WZDK27 38GS WZDK27 38GS WZDK27 38GS YSK68 4P Model 7K Cassette 9K Cassette 12K Cassette 18K Cassette Indoor fan motor WZDK37 38G WZDK37 38G WZDK37 38G YDK37 4P Model 9K Console 12K Console 18K C...

Страница 60: ...easure the resistance value with a tester Temperature Sensors Room temp T1 sensor Indoor coil temp T2 sensor Outdoor coil temp T3 sensor Outdoor ambient temp T4 sensor Compressor discharge temp T5 sen...

Страница 61: ...34105 116 0 40060 3 41 5878 37 5 87359 77 1 29078 117 0 38991 2 39 8239 38 5 62961 78 1 25423 118 0 37956 1 37 1988 39 5 39689 79 1 21330 119 0 36954 0 35 2024 40 5 17519 80 1 17393 120 0 35982 1 33 3...

Страница 62: ...5 234 9 35 35 78 75 8 084 115 2 422 4 222 8 36 34 32 76 7 82 116 2 357 3 211 4 37 32 94 77 7 566 117 2 294 2 200 7 38 31 62 78 7 321 118 2 233 1 190 5 39 30 36 79 7 086 119 2 174 0 180 9 40 29 15 80...

Страница 63: ...ure the resistance value of each winding by using the tester Position Resistance Value DA130M1C 31FZ DA150S1C 20FZ DA250S2C 30MT TNB306FPGMC L ASN108D22UEZ MNB36FAAMC L Blue Red 1 77 20 0 95 20 0 55 2...

Страница 64: ...W Red 4 Indoor AC Fan Motor Measure the resistance value of each winding by using the tester Posi tion Resistance Value RPG20D Weilng RPG28D T ongDe RPG28D Dayang RPG20E T ongDe RPG20E Weilng RPG13H W...

Отзывы: