8.
Electronic control function
8.1 Abbreviation
T1: Indoor ambient temperature
T2: Coil temperature of indoor heat exchanger middle.
T2B: Coil temperature of indoor heat exchanger outlet.
T3: Coil temperature of outdoor heat exchanger
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
Ts: Setting temperature
8.2 Electric control working environment.
8.2.1 Input voltage: 198V~264V.
8.2.2 Input power frequency:50Hz.
8.2.3 Indoor fan normal working amp. is less than 1A.
8.2.4 Outdoor fan. Normal working amp. is less than 1.5A.
8.2.5 Four-way valve normal working amp. is less than 1A.
8.3 Outdoor unit
’s digital display tube
There is a digital display tube in outdoor PCB.
Digital display tube display function
In standby , the LED displays “- -”
In compressor operation, the LED display the running frequency,
In defrosting mode, The LED disp
lays “dF” or alternative displays between running frequency and
“dF”(each displays 0.5s)
In compressor pre-
heating, The LED displays “PH” or alternative displays between running frequency
and “PH”(each displays 0.5s)
During the oil return process, Th
e LED displays “RO” or alternative displays between running
frequency and “RO”(each displays 0.5s)
In low ambient cooling mode, the LED displays “LC” or alternative displays between running
frequency and “LC”(each displays 0.5s)
In forced cooling mode,
the LED displays “FC” or alternative displays between running frequency and
“FC”(each displays 0.5s)
When PFC module protection occurs three times within 15 minutes,
the LED displays “E6” or
alternative displays between running frequency and “E6”(each displays 0.5s)
In protection or malfunction, the LED displays error code or protection code.
Содержание KAM2-42 DN5
Страница 11: ...10 4 Wiring Diagram KAM2 42 DN5 KAM2 52 DN5...
Страница 12: ...11 KAM3 80 DN5 KAM3 62 DN5 KAM4 80 DN5...
Страница 13: ...12 KAM4 105 DN5 KAM5 105 DN5 KAM5 120 DN5...