manualshive.com logo in svg
background image

2400 - 4400 VFX AERATOR MANUAL

10

The following is provided to help diagnose a probable source of trouble. It is a guideline only and may not show 

all causes for all problems. For additional troubleshooting help, contact your local distributor or visit 

kascomar-

ine.com

 for additional guidance. 

“My Aerator trips the ground fault interrupter in the C-25, C-85, or C-95.” 

This is the most common symptom of several possible problems. To correctly diagnose the problem, you will 

need to collect more information. A Ground Fault Interrupter (GFCI) breaker that trips can indicate an electrical 

service problem, water contamination in the unit and/or cord, bad breaker, control box problems, motor prob-

lems, etc. Try to find out the answers to these questions before you contact Kasco to narrow down the problem:

• 

How long does it take to trip the breaker? 

• 

Does it always take the same amount of time to trip? 

• 

How many times has it tripped? 

• 

Have there been any electrical problems in the area recently? 

“My Aerator seems to run slowly.” 

This can also be a symptom of several possible problems. There could be an electrical problem where the unit is 

not getting the proper voltage. This could also indicate a problem with the motor of the unit, which needs to be 

looked at by an Authorized Repair Center. Check that the unit is receiving the proper voltage, and, if so, contact 

Kasco for further steps. 

“My Aerator hums, but will not start. When I spin the prop with a stick, it starts up.” 

(single phase units only) This indicates a problem with the Starting Capacitor. Each Kasco aerator is equipped 

with a Starting Capacitor to get the unit going when it is first plugged in. If it is operating but not spinning and can 

be started by spinning the prop with a stick, the Starting Capacitor needs to be replaced by an Authorized Repair 

Center. 

“My Aerator turns itself off and back on without the timer and without tripping the GFCI breaker.” 

(single phase units only) Each Kasco aerator has a Thermal Overload built in that will turn the unit off when it 

overheats. Once the unit has cooled down, it will start back up. If you are noticing these symptoms, the unit 

should be unplugged immediately because the Thermal Overload will continue to turn on and off until it burns 

out and damages the motor. The unit should be unplugged and taken out of the water to find the cause of the 

problem. The problem could be one of many, such as, low water levels, build-up on the unit to prevent heat 

dissipation, something inhibiting the free rotation of the shaft, etc. If something is caught in the unit or there is a 

build-up of algae, calcium or organic matter on the unit, remove the debris and, if caught early enough, the unit 

should be fine. Contact a Kasco representative before restarting the unit. 

“My Aerator flow seems to fluctuate and/or be less than usual.” 

This can occur because of a few different reasons. Most of the time, this symptom is caused by the unit being 

clogged with debris. A mat of weeds, many leaves, plastic bags, etc. can clog up the unit and cause it to be starved 

of water. If the unit does not have the proper amount of water, the flow or pattern will fluctuate up and down 

and look sporadic. If you are seeing these symptoms, unplug the unit and clean away the debris that is clogging 

up the screen. Another possibility if these symptoms are noticed is a chipped or damaged prop that is causing 

the unit to wobble and not pump properly. When the unit is unplugged, check the prop for damages and replace 

if damage is found. 

“The GFCI breaker trips randomly and sporadically. Sometimes it is a few hours of operation, other times it can be 

days or weeks.” 

This is referred to as a Nuisance Trip. This usually occurs when the unit is installed a great distance from the 

initial electric service on the property where the ground stake is placed. It is caused by either induced current in 

the ground wire or a base voltage difference due to soil pH levels. To resolve the problem, contact an electrician 

and install a local grounding stake. This may eliminate the induced current and any base voltage differences. This 

problem can also be caused by a bad breaker or receptacle or having unbalanced incoming voltage lines.

TROUBLESHOOTING TIPS

Back to Contents

Содержание VFX

Страница 1: ...15 262 4488 sales kascomarine com kascomarine com MOVING WATER FORWARD SINCE 1968 Operation Maintenance Manual Document number 884170 Document version 2021 2 1 VFX DECORATIVE AERATOR 2400 3400 4400 30...

Страница 2: ...ABLE OF CONTENTS QUESTIONS Safety First 2 General Instructions 3 Unit Specifications Pattern Size 4 Parts Included 5 Unit Installation Instructions 7 Replacement Parts 8 Maintenance Recommendations 9...

Страница 3: ...h your control panel NEVER run the unit out of the water This will damage the seals and create a dangerous situation for the operator Use extreme caution around water especially cold water as in sprin...

Страница 4: ...balance It is extremely important to test the GFCI breaker in the control panel upon each installation re installa tion of the unit to ensure proper functioning Use Operation Kasco aerators are desig...

Страница 5: ...into C 25 3400VFX 5 5 ft 21 ft 110 120 7 3 18 C 25 plug in Plug into C 25 3400HVFX 5 5 ft 21 ft 208 240 3 7 9 Hardwire C 85 Plug into or hardwire C 85 4400VFX 8 ft 26 ft 110 120 11 3 40 C 25 plug in...

Страница 6: ...10 4 1 4 split washers 7 840537 5 1 4 3 4 OD flat washer 10 251300 6 1 4 20 x 1 3 4 hex head screw 3 475630 7 Bottom screen section 3 361540 8 1 4 20 nut 3 840536 9 8 nut 6 771034 10 8 flat washer 12...

Страница 7: ...ock washer goes between bolt and flat washer Tighten down in 4 places 3 4 5 9 10 11 12 10 3 Turn over Bring bottom screen sections together 8 4 5 5 6 ASSEMBLY INSTRUCTIONS 4 Tighten down in 6 places t...

Страница 8: ...n ponds where the water level fluctuates signifi cantly a small weight may need to be suspended at the midpoint of the rope to take up any slack caused by a drop in water level 1 foot of 1 galvanized...

Страница 9: ...0VFX 1 240595 5B Prop 3400VFX 3400HVFX 1 340595 5C Prop 4400VFX 4400HVFX 1 440600 6A Top disk 2400VFX 1 241025 6B Top disk 3400VFX 3400HVFX 1 241035 6C Top disk 4400VFX 4400HVFX 1 241045 7 O ring 1 99...

Страница 10: ...l lubrication of seals units that sit upright for many months or years have a greater likelihood of seals drying out CLEANING Aerators should be removed from the water at least once per year at the en...

Страница 11: ...when it overheats Once the unit has cooled down it will start back up If you are noticing these symptoms the unit should be unplugged immediately because the Thermal Overload will continue to turn on...

Страница 12: ...zinc anode around the motor shaft shows significant deterioration not maintained ac cording to Recommendations supplied in this Owner s Manual Warranty Claim Procedure The best method for establishin...

Страница 13: ...re rejected for repair will be destroyed unless otherwise directed by the customer Re jected equipment can be returned at the customer s expense for shipping and handling charges Billing All non warra...

Страница 14: ...ment or wastewater application circle one Yes No Additional notes Kasco Marine 800 Deere Road Prescott WI 54021 Attn Repairs Kasco requires that all equipment sent for repair MUST be accompanied by th...

Отзывы: