10

disconnection means.
C-85 panel requires at least a 30amp protected circuit 
feeding the panel.
C-95 panel requires at least a 40amp protected circuit 
feeding the panel.

Connect your power feed as detailed in the wiring 
diagram provided with this panel.

L1 connects to Terminal  

#1

L2 connects to Terminal  

#2

N connects to Terminal  

 N

G connects to Terminal 

GROUND  - 

located on  

    chassis 

plate

Be sure to provide adequate sized power conductors 
to prevent excessive voltage drop.  Consult with your 
electrician to properly size power feed conductors.  
Use copper conductors only.

Aerator power cord connection:

Your aerator (pump) will be provided with a flexible 

power cord for connection to this control panel.  If 
the power cord has a plug, you will need to cut it off.  
The power cord conductors (black, white, green) will 
need to be stripped back 1/2”.  The outer black jacket 
should be stripped back at least 3inches.  Follow the 
connection diagram for terminating these three wires 
to the terminal blocks in the control panel.

Black connects to Terminal   #4
White connects to Terminal   #5
Green connects to Terminal    G

Light Kit connection:

If you purchased a Kasco light kit(s) for your aerator, 
follow the light kit installation instructions for 

mounting the light kit(s) to the aerator float. 

This control panel requires a hardwire connection for 
the light kit(s).  To connect the light kit(s) you will 
need to cut off the power cord plug that is molded to 
the light kit power cord.  Strip back the black outer 
jacket of the light kit power cord at least 3inches 
to reveal the three internal wires of the power cord.  
(black, white, and green conductors).  These three 
wires will need to be stripped back 1/2”.  Follow the 
connection diagram for terminating these three wires 
to the terminal blocks in the control panel.

Control Panel Installation

STEP ONE
Inspect the panel for any damage and any components 
that may have loosened during shipping.

Control panel must be installed a minimum of 5ft (3m 
in Canada) from the inside wall of the pond, unless 
separated from the body of water by a fence wall, 
or other permanent barrier that will make the unit 
inaccessible to persons in the water.

Install the control panel to a post structure, side of a 
building, or other reliable means.  This structure must 

support the panel and prevent movement/flexing of the 

panel.  Use #10 x 1” or longer screws in the mounting 
points of the control panel to secure to the post 
structure.  NOTE:  The control panel must be hung 
upright in order to be waterproof.  It is also advised 
to mount the panel out of direct sunlight if possible.  
Mounting the panel in a North direction will prevent 
heat buildup inside the panel.  Also, mount the panel 

above the potential flood plain to prevent water entry 

during a possible flood event.

STEP TWO
Set Timer in the control panel to desired ON and OFF 
times per the Instructions on the door label or the 
instructions in this manual. 

STEP THREE
Electrical Service wiring:  

Follow all local and national electrical codes for 

this installation and Consult a qualified electrician 

or service person if needed.

All electrical connections to this panel must be made 

with proper strain relief cord grip fittings or with 

conduit connections as required by local and national 
electric codes.  The bottom of the enclosure is reserved 

for field installation of these connections.

3 phase:  (2.3, 3.3, 5.3, 7.3)
Refer to your 3 phase control panel instructions. 

Single Phase:  (8400, 3.1, 5.1) 

C85 / C95 non-metallic control panel:

Incoming power connection: (Power feed)

This control panel requires a 240V or 208V - 4 wire 
service (L1, L2, N, & G) and must be fed with a 
power circuit protected by a circuit breaker or a fused 
disconnect switch to provide circuit protection and a 

Содержание 8400JF

Страница 1: ...non metallic and 3 Phase Control Panel Timer pg14 8400JF Replacement Parts pg15 2 3JF Replacement Parts pg16 3 1JF Replacement Parts pg17 3 3JF Replacement Parts pg18 5 1JF Replacement Parts pg19 5 3...

Страница 2: ...al grounding conductor and or a grounding type attachment plug To reduce the risk of electrical shock be certain the aerator is properly connected to the Kasco supplied control panel re fer to the C 8...

Страница 3: ...lied to the aerator motor Unit should be protected by a GFCI Control panels must be installed by a qualified electrician See Installation instructions Kasco aerators are lightweight energy efficient a...

Страница 4: ...F 3 3JF 5 1JF 5 3JF 7 3JF Control Panel in separate box 1 if purchased Set of Interchangeable Nozzles 5 Diagrams Item Part Qty 1 6 x 1 2 Self Tap Screw 820405 3 2 3 8 x 4 bolt 820090 1 3a Linden Nozzl...

Страница 5: ...rough the assembly This may require some minor repositioning of the float sec tions as you push the bolt all the way through Do not force the bolt through Repeat for the remaining two joints 4 Turn th...

Страница 6: ...e Redwood nozzle make sure the Y Insert Part D4 is installed and seated properly into the Nozzle Housing Part D7 Push the nozzle down over the cone assembly it may require light taps with a rubber mal...

Страница 7: ...ou receive a 3 chain strain relief 6 or 8 gauge cord attach one chain to each of the three lower float brackets If there is not Strain Relief use the Nylon Cable Tie provided to secure the cord to a r...

Страница 8: ...nozzles available for the J Series Decorative Aerators Premium nozzles offer splendid beauty above and beyond our included patterns Madrone Premium Nozzle The Willow nozzle marked W on the inside of...

Страница 9: ...horizontally from the float For ease of removal you may choose to keep at least one anchor within reach from shore just below the water s surface ALTERNATE INSTALLATION In ponds where the water level...

Страница 10: ...blocks in the control panel Control Panel Installation STEP ONE Inspect the panel for any damage and any components that may have loosened during shipping Control panel must be installed a minimum of...

Страница 11: ...ow be installed per Instructions included with the lights Once completed power can be restored to the panel Record the following data while the Aerator is operating in the water under load Voltage L1...

Страница 12: ...12 C85 C95 non metallic Wiring Diagram C95 uses 30 Amp breaker...

Страница 13: ...gizing the panel 2 Verify the electrical service voltage and Phase matches the control panel and aerator nameplates ratings Refer to the control panel instructions and schematics for installation deta...

Страница 14: ...push trippers to the outside c Each tripper represents 15 minutes activation time Push as many trippers back as desired for dura tion time When the timer reaches the rst tripper the timer SPDT contact...

Страница 15: ...5 SCREW 10 24 X 2 5 LONG 3 6 840260 IMPELLER 8400 1 7 475642 WASHER 1 2 2 8 840235 BASEPLATE 2 3 5 HP J SERIES 1 9 840475 ZINC ASSEMBLY 1 10 840510 DEBRIS FLINGER 625 DIA SHAFT 1 11 990280 SEALING PLU...

Страница 16: ...ER 10 3 5 475625 SCREW 10 24 X 2 5 LONG 3 6 360100 IMPELLER LOCK NUT 1 7 840261 2 HP IMPELLER 1 8 475642 WASHER 1 2 2 9 840235 BASEPLATE 2 3 5 HP J SERIES 1 10 840475 ZINC ASSEMBLY 1 11 990290 O RING...

Страница 17: ...5626 FLAT WASHER 10 3 5 475625 SCREW 10 24 X 2 5 LONG 3 6 840360 IMPELLER 3 HP 1 7 475642 WASHER 1 2 1 8 840235 BASEPLATE 2 3 5 HP J SERIES 1 9 840475 ZINC ASSEMBLY 1 10 990280 SEALING PLUG 1 11 99027...

Страница 18: ...HER 10 3 5 475625 SCREW 10 24 X 2 5 LONG 3 6 840360 IMPELLER 3 HP 1 7 475642 WASHER 1 2 1 8 840235 BASEPLATE 2 3 5 HP J SERIES 1 9 840475 ZINC ASSEMBLY 1 10 990280 SEALING PLUG 1 11 990281 O RING 1 12...

Страница 19: ...LAT WASHER 10 3 5 475625 SCREW 10 24 X 2 5 LONG 3 6 840560 IMPELLER 5 HP 1 7 475642 WASHER 1 2 1 8 840235 BASEPLATE 2 3 5 HP J SERIES 1 9 840475 ZINC ASSEMBLY 1 10 990280 SEALING PLUG 1 11 990281 O RI...

Страница 20: ...3 5 475625 SCREW 10 24 X 2 5 LONG 3 6 360100 IMPELLER LOCK NUT 1 7 840561 5 HP IMPELLER 1 8 475642 WASHER 1 2 1 9 840235 BASEPLATE 2 3 5 HP J SERIES 1 10 840475 ZINC ASSEMBLY 1 11 990280 SEALING PLUG...

Страница 21: ...FLAT WASHER 10 3 5 475625 SCREW 10 24 X 2 5 LONG 3 6 360100 IMPELLER LOCK NUT 1 8 475642 WASHER 1 2 1 9 840475 ZINC ASSEMBLY 1 10 702300 PUMP BASE 7 HP 1 11 990280 SEALING PLUG 1 12 990290 O RING 1 1...

Страница 22: ...e ice thicker on the pond lake Storage over winter is best in a location that is out of the sun and cool but above 32 O F When storing units during the offseason it is important to store them upside d...

Страница 23: ...motor assemblies will be ac cepted for warranty repair The power cord and all other components must be returned with the motor as originally assembled Any missing parts will be re placed at the custom...

Страница 24: ...rews are tight and the nozzle looks centered you can reattach the cone assembly to the baseplate Make sure the cone assembly does not have any gaps with the baseplate before tightening the 3 screws My...

Страница 25: ...less than usual This can occur because of a few different reasons Most of the time this symptom is caused from unit being clogged with debris A mat of weeds many leaves plastic bags etc can clog up th...

Страница 26: ...panel with unit unless otherwise instructed A fee of 60 per hour will be assessed for cleaning excessively dirty units and float disassembly Refer to the Owner s manual for easy to follow troubleshoot...

Страница 27: ...27...

Страница 28: ...3 1JF _______________________________ Serial Ex 8001J311725 ______________________________ Purchase Date _____________________ Purchased From ___________________________________ Registration Date ____...

Отзывы: