3 Phase Startup Procedure

A Control Panel is not provided with your unit, please refer to the following warnings:

When inherent overheating protection is not provided: use with approved motor control that matches motor input in full load amperes 

with overload element(s) selected or adjusted in accordance with control instructions.  

Proper ground fault protection (RCD) must be provided at time of installation in your control panel

Note: The motor input in full load amperes is the marked value or the service factor amperes, shown on the namplate. 

 

3 phase

190 volt

2.3EJ

3.3EJ

3.3EVX 5.3EJ

Full load 

amps

6.4

10

9.6

15.2

Control panels must be installed by a qualified electrician.

If unit is connected to a circuit protected by a fuse, use a time-delay fuse with this pump.

You must verify motor rotation before installing the unit in the water.   

3phase Kasco units will run in a clockwise rotation when looking down at the propeller/impeller.  On J series units the upper pump 

housing must be removed to see the propeller/impeller.  Stand clear of the propeller/impeller while verifying rotation.  Follow the 

steps below.

Electrician:

1. 

Verify all screw terminal connections are tightened to specified torque setting prior to energizing the panel. 

2.  Verify the electrical service (voltage and Phase) matches the control panel and aerator nameplates ratings.  Refer to your control panel 

instructions and schematics for installation details. 

3.  Verify all switches, circuit breakers, and motor starters are in the OFF position 

4.  Connect electrical service to your control panel as shown in the electrical schematic that came with the panel. 

5.  Connect the unit power cord to the panel as shown in the electrical schematic with your panel

6.  Set the motor starter overload to the FLA rating on the aerator nameplate.

7.  Pump rotation:  Remove the upper pump housing (if you have a J series aerator) by removing the three screws attaching it to the lower 

pump housing.  The pump rotation is clockwise when looking down at the propeller/impeller.  Apply power to the control panel. 

Turn on the 15amp control circuit breaker, and motor starter.

8. 

Momentarily turn the Hand-Off-Auto switch to Hand.  This will run the aerator. Do not run the aerator for more than a few seconds on 

shore.  If the rotation is not correct.  Disconnect and lock out power from the control panel.  Swap any two of the aerator power 

cord wires in the panel.  This will cause the motor to reverse direction.  Reapply power to the panel and verify the rotation is 

clockwise.  

9. 

Once rotation is verified, with the power disconnected and locked out again, reinstall the upper pump housing.  Run the aerator 

one more time momentarily on shore to ensure the housing was reinstalled correctly. Disconnect and lock out power again and 

continue with installation of the aerator as detailed in the aerator owner’s manual.

Record the following data while the unit is operating in the water under load:

Voltage: 

 

  Amperage:

L1-L2 ____________ 

 

L1_______________

L1-L3 ____________ 

 

L2_______________

L2-L3 ____________  

L3_______________

Current unbalance should not exceed 5% at full load

.

3 phase 

380 volt

2.3HEJ

3.3HEJ 3.3HEVX 5.3EHJ

Full load 

amps

3.3

5

4.8

7.7

Содержание 4400EJ

Страница 1: ...Safety Instructions pg2 General description of equipment and function pg2 Intended use and limits of use pg2 Installation requirements pg3 Unit Specs pg3 Utility requirements pg3 Quick Disconnect Ins...

Страница 2: ...ase motor control motor starter with overload and short circuit protection must be provided at time of installation 3 phase units 2 3 3 3 5 3 require a startup test after wiring to ensure proper rotat...

Страница 3: ...talled This equipment is intended to operate without interaction from personnel Never to be manipulated moved maintained or ad justed while in operation Damage or injury could result The general publi...

Страница 4: ...slot for a flat blade screwdriver in the center of the insert Note The inserts have a LEFT HAND THREAD and should be turned clockwise to remove STEP TWO Remove the gland nut and gland from the rear of...

Страница 5: ...onal removal your quick disconnect includes an optional water tight cover Simply separate the quick disconnect and insert the sealing cover into the large blue nut half and tighten firmly Strain Relie...

Страница 6: ...O D of Cord Grey 7 9mm White 9 11mm Black 11 13mm Yellow 13 15mm Kasco 50 Hz Equipment Wire Size Chart Model Cord length 10m 30m 60m 90m 4400EJ 1 5mm 2 1 5mm 2 2 5mm 2 4mm 2 8400EJ 1 5mm 2 2 5mm 2 4mm...

Страница 7: ...Washer 3 840325 4 Float Single Piece 1 See Table Below 5 Interchangeable nozzles 5 See Nozzles Section 6 Nozzle oring 1 841217 7 Large JF Unit Assembly 1 See Table Below 8 Bottom Screen 1 See Table B...

Страница 8: ...8 1 2 4 7 3 10 11 1 2 3 Dedicated power cord channel Align with Cord Assembly Instructions Align slots with threaded holes Leave gap...

Страница 9: ...9 5 4 8 5 3EJ 9 Tighten 3 screws Twist Power cord cord with strain relief cord without strain relief OR cable tie mesh screen 5 3EJ...

Страница 10: ...2 3 2 4 8400 2 3 3 5 3 3 1 3 3 4 9 2 7 5 3 5 8 3 Spruce 5 4400 4 7 2 1 8400 2 3 6 6 2 7 3 1 3 3 7 2 7 5 3 7 9 2 7 Redwood 5 and 6 4400 4 9 1 5 8400 2 3 6 9 1 8 3 1 3 3 7 2 1 8 5 3 8 1 1 8 Pre Installe...

Страница 11: ...11 Balsam 1 Linden 1 Birch 4 Spruce 5 Redwood 5 Balsam Linden Oring dielectric grease Nozzle Assembly...

Страница 12: ...are in the OFF position 4 Connect electrical service to your control panel as shown in the electrical schematic that came with the panel 5 Connect the unit power cord to the panel as shown in the elec...

Страница 13: ...cantly you may need to suspend a small weight 30cm of 2 54cm galvanize pipe works well at the mid point of the rope to take up any slack as the water level drops The weight should be light enough so t...

Страница 14: ...in a location that is out of the sun and cool but above 0o C CLEANING Equipment should be removed from the water at least once per year at the end of the season in cold climates to clean the exterior...

Страница 15: ...from electrical power Check the propeller Impeller for any chipping or damage that would cause the unit to not operate properly Refer to installation instructions for assembly Replace propeller impel...

Отзывы: