The RJ12 connector offers two possibilities for wiring, either a switch to GND or a 12V output. If the
12V output is used, the power for the relay coil is supplied by the Kanomax AC/DC adaptor. In this
case, ensure that the relay coil does not draw more than 150mA and that a protection diode is
inserted across the relay coil.
If the switch to GND output is used, ensure that the relay coil does not draw more than 150mA, that
the voltage does not exceed 24V and that a protection diode is inserted across the relay coil.
5.1. Wiring for Alarm
The high alarm and low alarm pins can be wired to supply simple on / off switching to operate
equipment which requires only an on or off signal, such as an alarm.
To switch to GND use pins 4, 5 and 6. For a 12V output wire to pins 4, 5 and 1 (see the following
diagram for typical wiring for high alarm). This feature will only operate while powered by the AC
adaptor.
High gas level alarm
Note: Failure to insert a circuit protection diode, shown as above, will result in damage to the
monitor if a voltage spike is created by the relay.
5.2. Wiring for Control
The control pin can be wired to supply control of a gas concentration between upper and lower
concentration limits. The upper and lower limits can be set by the user. The factory default settings
are dependent on the gas sensor head selected at time of purchase.
To switch to GND use pins 3 and 6. For a 12V output wire to pins 3 and 1 (see following diagram for
typical wiring). This feature will only operate while powered by the AC adaptor.
Control is achieved by using a software latch. If power is lost to the monitor, the switch will open and
therefore turn off the external device connected to the monitor external output. The following wiring
diagram demonstrates the typical wiring to achieve the required control.
Page | 19
Kanomax Gasmaster User Guide
MRK-D-0002 V3