Supplied By www.heating spares.co Tel. 0161 620 6677
KANE455
manual
Page
19
4.4 DIFFERENTIAL
TEMPERATURE
Select “Diff Temp” to measure flow, return and differential temperatures
DIFF TEMP display
TEMP
→
Pump stops automatically when dial is
moved to Diff Temp.
T1
60.4
→
Use the T1 connection for the flow
temperature sensor.
T2
55.2
→
Use the T2 connection for the return
temperature sensor.
∆
T
5.2
→
Real time temperature difference.
Press
/
to print a differential temperature test (also sends to PC if
Bluetooth fitted).
Hold
/
for 2+ seconds to log a differential temperature report.
Viewing / printing a differential temperature test
Select MENU / REPORT / TEMP / VIEW
Use
or
to select the log number to be printed.
Press
/
to print the test (also sends to PC if Bluetooth fitted).