USING THE ANALYSER:
4.1 COMBUSTION
TESTS:
Insert the tip of the flue probe into the centre of the flue. The readings will
stabilise within 60 seconds assuming the boiler conditions are stable.
The rotary switch can be used to display the following information:
RATIO Display
NAT GAS
→
Defaults to natural gas on start-up. Can be
changed via “Menu”.
R 0.0008
→
CO/CO
2
ratio.
CO
52
→
Carbon
monoxide
(ppm).
CO
2
6.3
→
Carbon dioxide (%).
Press
/
to print a full combustion test (also sends to PC if
Bluetooth fitted).
Hold
/
for 2+ seconds to log a full combustion report.
O2/EFF display
O
2
9.8
→
Oxygen (%) left after combustion. Should
be 20.9% +0.1% in fresh air.
TF
145.1
→
Flue temperature (
o
C).
TI
5.4
→
Inlet temperature (
o
C). Normally set by
flue probe during fresh air purge.
Ef C
91.3
→
Defaults to condensing boiler efficiency
(EfC). Can be changed via “Menu”.