14
Kamstrup A/S • 5512603_C1_GB_03.2016
MULTICAL® 801
7
Electrical connection
The temperature sensors are
mounted in the terminals of the
calculator as shown above. Jumpers
are used when mounting 2-wire
sensors.
In connection with flow sensors
V1 and V2, the below-mentioned
colours are used for connection of
ULTRAFLOW® and electronic pick-up
units.
Flow sensors with Reed switch
output must be connected
to terminals 11-10 and 11-69,
respectively.
V1
V2
-
11
11
Blue
+
9
9
Red
SIG
10
69
Yellow
4-wire
51 51A 52A 52 3 7
8 4
1
5
6 2
T3
T2
T1
Pt
Pt
Pt
2-wire
51 51A 52A 52 3 7
8 4
1
5
6 2
T3
T2
T1
Pt
Pt
Pt
Terminal
No.
Standard
measurement of
heat and cooling
Heat
measurement and
leak surveillance
Energy
measurement
in open systems
T1
1–5–6–2
Sensor in inlet pipe
(red)
Sensor in inlet pipe
(red)
Sensor in inlet pipe
(red)
T2 3–7–8–4
Sensor in outlet
pipe (blue)
Sensor in outlet
pipe (blue)
Sensor in outlet
pipe (blue)
V1
11–9–10
Flow sensor in
inlet or outlet pipe
Flow sensor in
inlet pipe
Flow sensor in
inlet pipe
V2 11–9–69
-
Flow sensor in
outlet flow pipe
Flow sensor in
outlet pipe
T3 51–51A–
52A–52
-
Tank/heat
exchanger
temperature
Reference sensor
(grey)
Other makes of flow sensors are usually connected to terminals 10B and 11B.