Electrical wiring
IMPORTANT NOTE!
Condensation formation in the cooling unit!
In the event of on-site valve control, the cooling valve must be closed when the fans are switched off.
7.1
Maximum electrical rating values
Venkon XL, electromechanical model (*00)
Model
Number of
fans
Nominal
voltage
Mains fre-
quency
Nominal
power
Nom-
inal
current
Leakage
current
Ri ana-
logue in-
put
Protection
rating
Protection
class
1
1x Single
230 V AC
50 Hz
90 W
0.76 A
< 3.5 mA
100 KΩ
IP21
I
2
1x Tandem
230 V AC
50 Hz
178 W
1.45 A
< 3.5 mA
100 KΩ
IP21
I
3
1x Single, 1x
Tandem
230 V AC
50 Hz
297 W
2.32 A
< 3.5 mA
50 KΩ
IP21
I
4
2x Tandem
230 V AC
50 Hz
377 W
2.93 A
< 3.5 mA
50 KΩ
IP21
I
Tab. 10: Maximum electrical rating for Venkon XL EC, electromechanical model (*00)
Venkon XL, KaControl model (*C1)
Model
Number of
fans
Nominal
voltage
Mains fre-
quency
Nominal
power
Nom-
inal
current
Leakage
current
Ri ana-
logue in-
put
Protection
rating
Protection
class
1
1x Single
230 V AC
50 Hz
90 W
0.76 A
< 3.5 mA
20 KΩ
IP21
I
2
1x Tandem
230 V AC
50 Hz
178 W
1.45 A
< 3.5 mA
20 KΩ
IP21
I
3
1x Single, 1x
Tandem
230 V AC
50 Hz
297 W
2.32 A
< 3.5 mA
20 KΩ
IP21
I
4
2x Tandem
230 V AC
50 Hz
377 W
2.93 A
< 3.5 mA
20 KΩ
IP21
I
Tab. 11: Maximum electrical rating for Venkon XL EC, KaControl (*C1)
Содержание Venkon XL
Страница 2: ......
Страница 5: ...5 13 2 ERP Datenblatt Venkon XL 70...
Страница 67: ...Venkon XL Beschreibung Assembly installation and operating instructions 67 13 Certificates...
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ...www kampmanngroup com hvac products fan coils venkon xl 02 20 ENSAP Nr 1374732...