Cassette UniLine

 

Assembly and Installation Instructions

 

Keep these instructions in a safe place for future use! 

I164 11/20 GB  SAP-Nr. 1021206

Kampmann.de/installation_manuals

Содержание UniLine 10

Страница 1: ...Cassette UniLine Assembly and Installation Instructions Keep these instructions in a safe place for future use I164 11 20 GB SAP Nr 1021206 Kampmann de installation_manuals...

Страница 2: ...edrich Ebert Str 128 130 49811 Lingen Ems Germany T 49 591 7108 660 F 49 591 7108 173 E export kampmann de W Kampmann eu Kampmann UK Ltd Dial House Govett Avenue Shepperton Middlesex TW17 8AG Great Br...

Страница 3: ...n of remote sensor for outlet air temperature limit valve 14 7 Technical data 15 8 Commissioning 16 9 Maintenance 17 10 Electrical wiring 18 10 1 UniLine AC electromechanical model 00 19 10 2 UniLine...

Страница 4: ...ernal unit temperature sensor 46 10 9 Addressing Single circuit controls 47 10 10 Setting the unit configuration by means of DIP switches 48 10 11 Parameter settings 50 10 12 Parameter settings 51 10...

Страница 5: ...to tradespeople who are involved at the same time or subsequently as well as to end users or operators Retain these instructions until final decommissioning We reserve the right to make content or de...

Страница 6: ...eck the application with the manufacturer in the event of any doubt Any use other than the use specified above is deemed not to be correct and proper The operator of the unit is solely responsible for...

Страница 7: ...dentally re connected Wait until the fan has come to a standstill after the unit has been switched off before commencing installation maintenance work Caution Pipes casings and fittings can become ver...

Страница 8: ...DIN EN 14868 with regard to the properties of the medium used to protect the equipment The following values provide further guidance The water used should be free of contamination such as suspended su...

Страница 9: ...transport to avoid any damage to your health Store the units in dry dust free and weather proof rooms without any temperature fluctuations Never stack the units on top of each other to prevent damage...

Страница 10: ...5 with wall brackets 5 1 Installation dimensions of Cassette UniLine 1 Fixing points 2 Outlet air rectifier 3 Perforated plate with filter 4 Flow 3 4 5 Return 3 4 6 Opening for connecting cable for th...

Страница 11: ...2 Outlet air rectifier 3 Perforated panel with filter as air intake 4 Flow 3 4 5 Return 3 4 6 Opening for connecting cable for thermoelectric shut off valve accessory 7 Cable opening for electrical w...

Страница 12: ...p the pipework Remove the protective caps from the supply and return pipes Seal the valve connections and connect up securing the nut to prevent it from shearing or twisting Caution Use an appropriate...

Страница 13: ...alve and outlet air temperature limiting valve 1 Flow with air vent 2 Return with air vent 3 Outlet temperature limit valve type 100967 installation in the flow 4 Thermoelectric shut off valve type 10...

Страница 14: ...p 2 using the screws provided Remove the rectifier 3 on the left side of the unit Carefully route the remote sensor 4 through the opening in the outer wall 5 and the fan bracket 6 Press the remote sen...

Страница 15: ...urrent consumption A 1 82 2 67 3 70 4 75 Max electrical power consumption W W 382 565 757 940 Mains voltage V 230 230 230 230 Mains frequency Hz 50 50 50 50 Unit Cassette UniLine AC Model 10 15 20 25...

Страница 16: ...d and wired throughout Waterside connection Have the flow and return pipes been laid correctly and fault free Are the valves correctly fitted Are all valves and actuators fitted correctly Note the per...

Страница 17: ...cleaner Avoid damaging the pipes and fins Repair work on the fan and heat exchanger can be carried out with the service hatch open Please refer to the safety information given in point 2 1 1 2 2 Filt...

Страница 18: ...sed switching on Wire the units as per the wiring diagrams supplied with the units Carry out the electrical connection only in accordance with VDE and EN regulations currently in force as well as the...

Страница 19: ...ge switch as shown on the table if using Kampmann stage switches Parallel mode You can switch a maximum of two door air curtains in parallel via a cascade module type 100906 Extend the groups with the...

Страница 20: ...230 V 50 Hz Fuse by others to next cascade modul DDC release door contact or similar B 3 B A A 3 3 3 A Parallel operation of UniLine AC door air curtains Refer to the table below for the number of wi...

Страница 21: ...A When switching between the fan stages the power contactor temporarily disables the fans to avoid transverse voltage of the transformer Dip switch setting on the PCB Technical details for inputs out...

Страница 22: ...n W1 Spannungsversorgung W2 Steuersignal f r Gebl se Stellantrieb und St rmeldung Kabell nge max 30m Automa onssta on W2 Stellantrieb Typ 146905 AE1 1 COM SM SM 3 SM SM 4 SM SM 5 W2 W1 4 4 1 5 5 2 Dre...

Страница 23: ...de selector switch and speed sensor with options for external control and operation The required room temperature is set on the compact controller The door air curtain is disabled in standby mode A fr...

Страница 24: ...eschl TLS aktiviert 2 1 1 2 2 W4 2 W5 2 W5 T rlu schleier Ger t Nr 1 230V 50Hz UC 10V N PE L 1 2 3 7 6 1 2 GND 1 RI je nach Baugr e 33 50 100KOhm Stellantrieb Typ 146905 2 E T rlu schleier Ger t Nr 2...

Страница 25: ...oma onssta on 2 RI je nach Baugr e 33 50 100KOhm 3 W2 Stellantrieb Typ 146905 2 E 0 10 0 10 4 GND GND 5 2 VH VH 1 0 0 2 2 W2 W1 W3 W2 W1 W3 W3 W1 T rlu schleier Ger t Nr n 230V 50Hz UC 10V N PE L 1 2...

Страница 26: ...ntroller Combination of operating mode selector switch and speed sensor with options for external control and operation The required room temperature is set on the compact controller The door air curt...

Страница 27: ...13 DI 1 14 GND 2 T rlu schleier Ger t Nr 2 230V 50Hz GND A2 A1 0 10V 1 2 N PE L 1 2 3 A2 A1 1 2 NO COM 4 3 RI 100KOhm Stellantrieb Typ 146905 NC 10V Op onal Raumtemperatur f hler Typ 148921 2 1 1 2 O...

Страница 28: ...ungsversorgung W2 Steuersignal f r Gebl se und St rmeldung W3 Steuersignal f r Stellantrieb Maximale L nge der Leitung W2 30m Automa onssta on W2 Stellantrieb Typ 146905 NC 5 10V SM SM 3 SM SM 4 SM SM...

Страница 29: ...on with the manufacturer in the event of any doubt Any use other than the use specified above is deemed not to be correct and proper The operator of the unit is solely responsible for any damage arisi...

Страница 30: ...ature sensor for room temperature control Large LCD multifunctional display with clearly arranged icons Selection of value to be displayed room temperature setpoint offset setpoint Automatic LED backg...

Страница 31: ...switched off 5 seconds after the KaController has last been used The LED background lighting can be permanently disabled by a parameter setting 1 Display of setpoint room temperature 2 Current time 3...

Страница 32: ...dial or side function keys are also used to select the various selection menus 10 5 2 2 Operation Menu selection using function keys Default view Fan setting Time setting Timer programs Modes of opera...

Страница 33: ...stage set Switching off the control There are 3 options for switching off the control 1 Press the ON OFF button 2 Turn the navigator dial to the left until OFF appears 3 Press and hold down the naviga...

Страница 34: ...option of setting fan stages Auto 0 1 2 3 4 5 as required Pressing the navigator dial in the default view switches the display to the Fan setting menu You can select the required fan stage Auto 0 1 2...

Страница 35: ...ode The controller operates only in cooling mode Fan ON Heating ON The operating mode required can be selected by turning the navigator dial in the Operating mode selection menu Pressing the navigator...

Страница 36: ...ically called up once the current day has been confirmed by pressing the navigator dial If no action is carried out using the navigator dial or the functional keys for longer than 7 seconds the last c...

Страница 37: ...x the Clock symbol is hidden in the default view Display elements in the Timer programs selection menu ON1 OFF1 ON2 OFF2 MO 6 00 18 00 TU 6 00 18 00 WE 6 00 18 00 TH 6 00 18 00 FR 6 00 18 00 SA 8 00 1...

Страница 38: ...all up the next input screen Step 2 Turn the navigator dial to select the number of the timer program no 1 or no 2 Press the navigator dial to apply the value for instance Timer program no 1 and to ca...

Страница 39: ...switching on and switching off times entered Step 1 Step 2 Replace the switch on or off time entered by Step 3 Step 4 You can overwrite timer entries at any time either as a block or for each day Onl...

Страница 40: ...inimum of 10 seconds to call up the Service menu The display shows Para and then CODE with the value 000 in sequence 3 Select the code 44 by turning the navigator dial and confirm by pressing the navi...

Страница 41: ...m table KaController alarm table Code Alarm Priority A11 Faulty control sensor 1 A12 Motor fault local stop 2 A13 Room frost protection 3 A14 Condensation alarm 4 A15 General alarm 5 A16 Faulty AI1 AI...

Страница 42: ...ecting a KaController to it automatically converts the respective KaControl into the master unit in the control circuit Disconnect the unit prior to commencing all wiring work Only connect the bus lin...

Страница 43: ...sensor Any motor fault with a KaControl is shown on the KaController by the display A12 When a motor fault has occurred check whether the fan is blocked To eliminate the fault disconnect the unit and...

Страница 44: ...s switched on A16 Faulty AI1 AI2 or AI3 sensor The sensor alarm is displayed if one of the active sensors does not transmit any plausible measured values to the KaControl Check the correct wiring of t...

Страница 45: ...8 and at least of the same value When laying bus cables avoid the formation of star points for instance in junction boxes Pass the cables through to the units Wrong Star shaped wiring of the bus lines...

Страница 46: ...he wiring diagram and configure the functions by means of the KaController The maximum cable length between the master unit and the external potential free contacts is 30 m 10 8 3 External room temper...

Страница 47: ...unit by connecting the KaController The respective KaControl automatically becomes the master unit in the control circuit when a KaController is connected to it A master unit need not necessarily be...

Страница 48: ...rol unit to check and possibly adjust the DIP switches The DIP switches are factory set in accordance with the unit configuration Disconnect the control before starting to adjust the DIP switches Func...

Страница 49: ...mode winter mode changeover is set as standard using the KaController Alternatively summer mode winter mode changeover can also be performed by an external thermostat or an external switching contact...

Страница 50: ...ON OFF key or Pressing the navigator for a minimum of 5 seconds or Turning the navigator to the left until OFF appears 2 Press the navigator dial for a minimum of 10 seconds to call up the Service men...

Страница 51: ...y different perception of room temperature Alternately the setpoint can be set in absolute values Parameter P36 is used to configure the setpoint setting Use parameter P01 to configure the base setpoi...

Страница 52: ...on 2 Use the ON OFF key and the timer programs to switch the KaControl on and off Parameter P38 can also be set for the Winter summer changeover using clip on sensor function Section 10 3 7 10 12 2 ON...

Страница 53: ...on 1 ON OFF contact open ON 2 winter summer changeover contact open heating 3 Eco Day mode contact open Day 4 no function contact open without function 5 condensation alarm contact open no condensatio...

Страница 54: ...utput V2 The digital output V2 is used to control the heating valve in a 4 pipe system The digital output V2 can be configured using parameter P39 10 12 4 Function of digital outputs V1 and V2 Positio...

Страница 55: ...re sensor induction sensor 6 0 100 K ohm fan actuation 7 0 100 K ohm temperature setpoint 8 0 100V BMS winter summer control 9 0 100V BMS winter control 19 external frost protection monitor contact cl...

Страница 56: ...ir sensor 2 NTC cold hot water sensor clip on sensor 3 NTC cold water sensor clip on sensor 4 NTC hot water sensor 5 NTC external Room temperature sensor induction sensor 6 0 100 K ohm fan actuation 7...

Страница 57: ...t the password code 77 by turning the navigator dial and confirm by pressing the navigator dial 4 L01 is shown on the display and the functional testing of the connected assemblies can start Important...

Страница 58: ...of input AI3 0 0 9 0 P018 Temperature increase of cooling setpoint in Eco mode 30 0 255 K 10 30 P019 Temperature drop of heating setpoint in Eco mode 30 0 255 K 10 30 P020 ADC limit coefficient 6 0 15...

Страница 59: ...etpoint setting to the value of P01 after changing an operating programme 0 0 1 0 P058 Sensor calibration Sensor AI1 0 99 127 K 10 0 P059 reserved P060 reserved P061 Sensor calibration sensor in the K...

Страница 60: ...on limit 30 0 100 V 10 30 P099 Actuation 0 10V min fan speed switching on limit 40 0 100 V 10 40 P100 Actuation 0 10V max fan speed switching on limit 90 0 100 V 10 90 P101 Valve actuation by pulse w...

Страница 61: ...r dial for a minimum of 10 seconds The display shows Para and then CODE with the value 000 in sequence 3 Select the password code 11 by turning the navigator dial and confirm by pressing the navigator...

Страница 62: ...r calibration in KaController 0 60 60 C t006 LCD display contrast 15 0 15 t007 BEEP setting 0 BEEP ON 1 BEEP OFF 0 0 1 t008 KaController parameter menu password 11 0 999 t009 Minimum settable setpoint...

Страница 63: ...2 CANbus Karte Typ 3260301 3 W5 3 Einkreisregelung bis 6 Ger te Leitung W4 erforderlich gesamte maximale Leitungsl nge 30m Einkreisregelung bis 30 Ger te CANbus Karte und Leitung W5 erforderlich gesa...

Страница 64: ...3 W5 3 W4 N V1 Stellantrieb Typ 146905 N V1 Stellantrieb Typ 146905 N V1 Stellantrieb Typ 146905 3 GNX 1 2 3 1 2 W5 3 Netz 230VAC Absicherung Bauseits N 3 PE 1 L 2 3 W1 120 Ohm 120 Ohm Bedientableau...

Страница 65: ......

Страница 66: ...GmbH Co KG Friedrich Ebert Str 128 130 49811 Lingen Ems Germany T 49 591 7108 660 F 49 591 7108 173 E export kampmann de W Kampmann eu Kampmann UK Ltd Dial House Govett Avenue Shepperton Middlesex TW...