6.5
Condensation connection
6.5.1 Installing the condensation drain (with cooling units)
Condensate pump SI 30
The self-priming condensate pump is factory-connected to the top of the unit as far as the hose connection spigot for the on-
site condensate pressurised line.
Fig. 9: Condensation pump
Max. delivery height [m]
8 m with max. 4.5 l/h flow rate and a hose length of 10 m
Max. flow rate [l/h]
Approx. 18 l/h with 0.5 m delivery height and a hose length of 2 m
Supply voltage [V/Hz]
230 V/50 Hz (separate mains power line needed)
Power consumption [W]
14 W
Safety shut-off [A]
5 A resistive
Fuse [A]
Max. 16 A
Diameter of pressurised condensate line
DN 6 mm (hose connection)
Signal contact for condensate overflow
Normally closed (NC) contact, potential-free, switching capacity 250 V/5 A
Switched by "Hall effect"
Integrated thermal cut-out
Tab. 5: Technical data
Flow volumes and limits of use
The achievable flow volume depends on the delivery height and length of condensate hose connected. The volume of con-
densate rises and the possible delivery height of the pump falls with extreme air humidity and/or very low system temperat-
ures. Therefore set up the alarm contact of the float switch to stop dehumidification (e.g. by closing the cooling valve).
Note the following limits of use for max. permitted cooling conditions (CHW 6/10 °C with inlet air temperature 27°C / 60%
rel. humidity):
Model 85: Max. permitted delivery height with a 5 m hose length: 3 m
Model 96: Max. permitted delivery height with a 5 m hose length: 2 m
More powerful condensate pumps are available on request if the permitted flow rate is continually being exceeded.