Ultra
Assembly, installation and operating instructions
65
Parameter
Function
Standard
Min.
Max.
Unit
Ultra
10
P075
Serial address of Slave 5
0
0
207
-
0
P076
Serial address of Slave 6
0
0
207
-
0
P077
Serial address of Slave 7
0
0
207
-
0
P078
Serial address of Slave 8
0
0
207
-
0
P079
Serial address of Slave 9
0
0
207
-
0
P080
Serial address of Slave 10
0
0
207
-
0
P081
Dependence of the hydronic algorithms, Slave 1
0
0
7
-
0
P082
Dependence of the hydronic algorithms, Slave 2
0
0
7
-
0
P083
Dependence of the hydronic algorithms, Slave 3
0
0
7
-
0
P084
Dependence of the hydronic algorithms, Slave 4
0
0
7
-
0
P085
Dependence of the hydronic algorithms, Slave 5
0
0
7
-
0
P086
Dependence of the hydronic algorithms, Slave 6
0
0
7
-
0
P087
Dependence of the hydronic algorithms, Slave 7
0
0
7
-
0
P088
Dependence of the hydronic algorithms, Slave 8
0
0
7
-
0
P089
Dependence of the hydronic algorithms, Slave 9
0
0
7
-
0
P090
Dependence of the hydronic algorithms, Slave 10
0
0
7
-
0
P091
Load default values
0
0
255
-
0
P092
Password management
0
0
255
-
0
P093
Type of pre-comfort (room occupancy)
0
0
3
-
0
P094
Pre-comfort timer
60
1
255
min
60
P095
Disable DIP switch settings
0
0
1
-
0
P096
Digital outputs continuously activated
0
0
1
-
0
P097
Read DIP switch
-
0
63
-
-
P098
Activation 0..10V: switch on limit for valves
30
0
100
V/10
30
P099
Activation 0..10V: min. switch on limit for fan speed
40
0
100
V/10
40
P100
Activation 0..10V: max. switch on limit for fan speed
90
0
100
V/10
90
P101
Valve activation by pulse width modulation of P-band in
heating mode
15
0
100
K/10
15
P102
Valve activation by pulse width modulation of P-band in
cooling mode
15
0
100
K/10
15
P103
Valve activation by pulse width modulation of reset time of
PI controller
0
0
20
min
0
P104
Minimum ON time with valve activation PWM
3
0
20
min
3
P105
Compensation: max. negative delta setpoint
50
0
150
K/10
50
P106
Compensation: max. positive delta setpoint
50
0
150
K/10
50
P107
Duration of valve open to check water temperature
5
0
255
min
5
P108
Duration of valve closed
240
35
255
min
240
P109
Dead zone PI control for 3-way valve
10
0
100
K/10
10
P110
Hysteresis to switch between heating/fan operation
0
0
20
°C
0
P111
Threshold for switching between heating/fan operation
0
0
50
°C
0
P112
reserved
-
-
-
-
-
P113
reserved
-
-
-
-
-
P114
reserved
-
-
-
-
-
P115
reserved
-
-
-
-
-
P116
reserved
-
-
-
-
-
P117
Lock function buttons on KaController
0
0
7
-
0