10.3.3 Dismantling the housing cover
Note: Remove all snap hooks on the cover from their anchoring before dismantling (risk of breakage)!
Dismantle the housing cover for maintenance purposes and visual checks:
Fig. 32: Dismantling the housing cover
Important! Residual condensate can escape when dismantling the housing cover!
10.3.4 Cleaning the condensate tray
With the Ultra cooling model, the condensate tray also needs to be dismantled after the housing cover to provide access to
the unit for visual checks and any cleaning work needed.
Fig. 33: Unscrewing the plug-in nut on the con-
densate tray
Unscrew the plug-in nut on the condensate tray.
Important!
If the alarm has been triggered, there can be up to 1 litre of water
in the condensate tray! Drain this off through the drain connection before dis-
mantling the condensate tray.
Fig. 34: Lowering the condensate tray
Lower and remove the condensate tray.
When refitting, make sure that the condensate tray is correctly positioned in the
corners of the air intake crown.
Fig. 35: Cleaning the condensate tray
Remove any dirt in the condensate tray. Clean the condensate lines as well if
there is serious dirt in the condensate!