7.2
Electromechanical connection, 24 V (*24)
Wiring (*24)
All factory-fitted actuators are wired to terminals on the electromechanical model (*24).
The operating voltage must be provided by a voltage supply (24 V DC) by others.
Kampmann offers several different output classes of switched-mode power supply units (SMPS) as accessories for the
voltage supply.
The speed of the EC fans used can be continuously variably controlled by a 0-10 V DC signal. In the event of a motor
fault, the intelligent motor electronics switches off the fan automatically.
Note these points in the following wiring diagrams for PowerKon nano with electromechanical control:
Comply with the details on cable types and cabling with due consideration for VDE 0100.
Without *: NYM-J. The requisite number of wires, including protective earth, is stated on the cable. Cross-sections are
not stated, as the cable length is involved in the calculation of the cross-section.
With *: J-Y(ST)Y 0.8mm. Lay separately from power lines.
If other types of cables are used, they must be at least equivalent.
The terminals on the unit are suitable for a maximum wire cross-section of 2.5 mm².
The
need to be respected when rating the in situ mains power supply and fusing.
Содержание PowerKon nano
Страница 2: ......
Страница 16: ...PowerKon nano PowerKon nano Assembly installation and operating instructions 16...
Страница 17: ...PowerKon nano PowerKon nano Assembly installation and operating instructions 17...
Страница 18: ...PowerKon nano PowerKon nano Assembly installation and operating instructions 18...
Страница 19: ...PowerKon nano PowerKon nano Assembly installation and operating instructions 19...
Страница 20: ...PowerKon nano PowerKon nano Assembly installation and operating instructions 20...
Страница 38: ...PowerKon nano PowerKon nano Assembly installation and operating instructions 38 12 Certificates...
Страница 42: ......
Страница 43: ......