9
Katherm QE –
Tangential fan convection with electric heating element
2.42
Ready-to-install convector-based floor trenches
Assembly and installation instructions
Technical data
1)
The sound pressure levels were calculated with an assumed
room insulation of 8 dB(A). This corresponds to a distance of 2 m, a room volume
of 100 m³ and a reverberation time of 0.5 sec (in line with VDI 2081).
2)
Sound pressure level < 20 dB (A) and sound power level < 28 dB (A) outside the
usual measuring and audible range.
Fan stage
Contr
ol signal
Heat output
Electrical power
consumption fan
Curr
ent consump
-
tion
Sound pr
essur
e
level
1)
Sound power level
[V]
[W]
[W]
[A]
[dB(A)]
[dB(A)]
Trench length 825 mm
Boost stage
10
660
6
3.5
28
36
Design stages
8
530
5
2.8
26
34
6
400
4
2.1
21
29
4
260
3
1.4
< 20
²)
< 28
²)
Minimum stage
2
130
3
0.7
< 20
²)
< 28
²)
Trench length 1250 mm
Boost stage
10
1300
7
6.3
31
39
Design stages
8
1040
6
5.0
29
37
6
780
5
3.8
24
32
4
520
4
2.5
< 20
²)
< 28
²)
Minimum stage
2
260
3
1.3
< 20
²)
< 28
²)
Trench length 1700 mm
Boost stage
10
2000
7
9.6
33
41
Design stages
8
1600
6
7.7
31
39
6
1200
5
5.8
26
24
4
800
4
3.8
< 20
²)
< 28
²)
Minimum stage
2
400
3
1.9
< 20
²)
< 28
²)
Содержание Katherm QE