15
Katherm QE –
Tangential fan convection with electric heating element
2.42
Ready-to-install convector-based floor trenches
Assembly and installation instructions
Status coding of the red LED fault signal
Lights up
= Continuously lit
1 x flash
= On (0.2 sec.)
Off (0.8 sec.) ...
2 x flashes
= On (0.2 sec.)
Off (0.8 sec.)
On (0.2 sec.)
Off (2 sec.) ...
3 x flashes
= On (0.2 sec.)
Off (0.8 sec.)
On (0.2 sec.)
Off (0.8 sec.)
On (0.2 sec.)
Off (2 sec.) ...
Alternating
= On (0.5 sec.)
Off (0.2 sec.)
On (0.1 sec.)
Off (0.2 sec.) ...
DIP switch settings
LED status messages
In the event of impermissible temperature increase within the Katherm QE, for example
by increasing the temperature within the Katherm QE, an integrated two-stage safety
switch guarantees that the unit is properly switched off. At a temperature of 80°C within
the Katherm QE, the heating element is disabled.
A roll-up grille temperature of 45 Kelvin above the room temperature is maintained in
accordance with IEC EN 60335-2-30. The triggering of the safety temperature monitor
can be signalled via a potential-free fault alert contact. After rectifying the cause of the
fault, the fault message is acknowledged by resetting the supply voltage.
The speed of the EC tangential fan is also monitored.
Should no speed pulses of the EC tangential fan be generated because of the motor
coming to a standstill, the electric heating element is disabled.
Factory setting
OFF
ON
DIP 1
OFF
Enable not required
Enable required
DIP 2
OFF
Speed increase Off
Speed increase On
DIP 3
OFF
Minimum heat output = 20%
Minimum heat output = 30%
DIP 4
OFF
–
–
LED
Function
Colour
Status
Description
1
Heating
Yellow
Lights up
Heating mode
2
Fault message
Red
1x flashes
Fault of EC motor
2x flashes
EC motor speed
3x flashes
PCB temperature sensor has
triggered
Lights up
STB has triggered
3
Status
Green
OFF
No mains voltage or error
flashes cyclically
Operation
alternating fast-flow flashing
No enable
Lights up
Standby