clock thermostat, type 30056/146910
Page 19
Please mount the thermostat correctly so that the average room temperature can be
measured. (Avoid air inlet or installation near windows and doors). The thermostat should be
placed in inner walls in an approximate height of 1.5 m.
10. Technical data
Type 30056/146910
Temperature range
+5...+ 40°C
Temperature setback
2 ... 10K, adjustable
Temperature sensor
KTY (internal)
or
KTY (remote, please order separately)
Tolerance of sensor
±1K
Operating differential
±0,1...±3,0K adjustable
Proportional band
1...10K, adjustable
Width of pulse
1...15min, adjustable
Frost protection
+5…+15°C, adjustable
Temperature resolution
Nominal value 0,5K,
actual value 0,1K
Nominal temperature setting
rotary knobs, menu
Programme positions
16
Timer
Electronic 7-day timer
Battery storage reserve
1
approx. 4 hours
Visual indication
LC-display
Operating voltage
230V AC (±10%)
Power consumption
ca. 2VA
Relay contact
1 floating double-throw contact
Maximum permissible current
10(4)A, 230V AC
Electrical connections
screw terminals
Electrical lifetime
0,5 x 10
5
switching operations
Max. permissible ambient temperature
0...+ 50°C
Storage temperature
-10...+70°C
Enclosure: Material
plastic
Protective kind
IP 20
Protective class
II in accordance with EN 60730
Dimensions
132 x 82 x 32mm (W x H x D)
Mounting
Wall mounting or on flush box
Cable entry
for surface wiring or rendering
Weight
approx. 250 grams
1
The battery storage reserve only refers to time.
Any other parameter remain stored fix.