background image

 

 

Net: it is same to the Net ID set in the former serial port configuration window.   
COM no.: the PLC serial port no., here we use XD-NE-BD, so the port no. is COM4.   
Gateway: please keep it as default value 0.   
11. click write after setting all the things. It will show write config successful message. 
12. click confirm. Then cut off the PLC power supply and power on again. Now all the configuration is 
completed.     

Note:

 

1. after changing the device, it needs to configure again. 
2. if it shows the error message “Xnet server read config error”, please restart the software and configure 
again. 
Please refer to XD series PLC programming manual chapter 7 for X-NET and Modbus communication 
details.   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание XINJE XD series

Страница 1: ...XD series BD board...

Страница 2: ...system error the output will lose control when the PLC circuit has problem Please design suitable external control circuit to ensure the device working normally If the PLC relay or transistor unit is...

Страница 3: ...extend BD board Table 1 XD series extension BD board specifications Installation mode Install in the XD series PLC directly Dimension 40mm 42mm 14mm Using environment No corrosive gas Environment temp...

Страница 4: ...Wiring terminal Left side is signal input right side is signal output Dimension and installation Installation XD extension BD board can be installed in the COM4 or COM5 of XD series PLC Please remove...

Страница 5: ...tware can set two communication mode including Modbus and XNET XINJEConfig software installation XINJEConfig software is inside XDPpro software installation package please open it and install as the g...

Страница 6: ...LC then click confirm Then back to main window click Config single device com port 4 it will show the com port setting window 5 As XD3 32T E only can connect one BD board which is COM4 here we set Com...

Страница 7: ...servo Baud rate for this application 1 5M Token cycle time each station cycle once in the same network the unit is ms For this application there are only two PLC so we set it to 10ms Max station numb...

Страница 8: ...things It will show write config successful message 12 click confirm Then cut off the PLC power supply and power on again Now all the configuration is completed Note 1 after changing the device it nee...

Страница 9: ...www kalatec com br Instagram kalateceautoma o Facebook kalatecautoma o NOSSAS FILIAIS Matriz Campinas SP Rua Salto 99 Jd do Trevo 19 3045 4900 Filial S o Paulo SP Av das Na es Unidas 18 801 11o Andar...

Отзывы: