background image

 

 

 

Electric design reference                                                                   

Configuration mode 

 

XD-NS-BD can be used to communicate between the XD series PLC, XD PLC and other devices 
through RS232.   

 

XD-NE-BD can be used to communicate between XD series PLC, TN series HMI, DS3E series 
servo drive, other devices through RS485 or fieldbus(X-NET).   

 

XD-NO-BD can be used to communicate between XD series PLC through RS485 or fieldbus(X-
NET). 

 

XD series extension BD board needs special software XNETConfig to configure. This software can set 
two communication mode including Modbus and XNET.   

XINJEConfig software installation 

XINJEConfig software is inside XDPpro software installation package, please open it and install as the 
guide. Please install and run “as administrator”. 

XINJEConfig using steps 

Here is an example of communicating between two XD3-32T-E PLC through XD-NE-BD via X-NET.   

Note: 

please use USB cable connect PLC with PC when configurating the BD board.   

 

USB cable needs to install the USB driver, please download o

www.xinje.com

.   

1. 

Open the XINJEConfig, it will show below window: 

 

2. click Config/Find device, it will show below window: 

COM

42.1

39.4

COM

A B

42.1

39.4

COM

COM

42.1

39.4

Содержание XINJE XD series

Страница 1: ...XD series BD board...

Страница 2: ...system error the output will lose control when the PLC circuit has problem Please design suitable external control circuit to ensure the device working normally If the PLC relay or transistor unit is...

Страница 3: ...extend BD board Table 1 XD series extension BD board specifications Installation mode Install in the XD series PLC directly Dimension 40mm 42mm 14mm Using environment No corrosive gas Environment temp...

Страница 4: ...Wiring terminal Left side is signal input right side is signal output Dimension and installation Installation XD extension BD board can be installed in the COM4 or COM5 of XD series PLC Please remove...

Страница 5: ...tware can set two communication mode including Modbus and XNET XINJEConfig software installation XINJEConfig software is inside XDPpro software installation package please open it and install as the g...

Страница 6: ...LC then click confirm Then back to main window click Config single device com port 4 it will show the com port setting window 5 As XD3 32T E only can connect one BD board which is COM4 here we set Com...

Страница 7: ...servo Baud rate for this application 1 5M Token cycle time each station cycle once in the same network the unit is ms For this application there are only two PLC so we set it to 10ms Max station numb...

Страница 8: ...things It will show write config successful message 12 click confirm Then cut off the PLC power supply and power on again Now all the configuration is completed Note 1 after changing the device it nee...

Страница 9: ...www kalatec com br Instagram kalateceautoma o Facebook kalatecautoma o NOSSAS FILIAIS Matriz Campinas SP Rua Salto 99 Jd do Trevo 19 3045 4900 Filial S o Paulo SP Av das Na es Unidas 18 801 11o Andar...

Отзывы: