Solutions flowchart – TWIN ultrasound 

Is ignition sparking?

 

Ignition sparks, does the 
pilot light go on?

 

Does the pilot light come 

on when ignition button is 

held pushed in and being 

released after 20 sec.?

 

 

Burner bed comes on

 

The thermocouple is 

broken. 

Contact your dealer.

 

Check that ignition cable is hanging free 
and not clamped against an iron 
component, or this sparks continuously.

 

There may be turbulence in the 
pilot light, which means it is being 
blown away. This could be 
because the chips are lying in 
front of the pilot light. Reposition 
them and try again

 

Check whether the distance between 
ionization pen and thermocouple is 
not too great to spark across. If 
necessary, bend closer.

 

Nee

No

 

Ja

Yes

 

No

 

Yes

 

No

 

Contact your dealer

 

Check whether the gas tap is 
open or that there is a blockage 
in the gas supply

 

No

 

No

 

Yes

 

Yes

 

.

Does the microswitch shut off 

the tube of the pilot light ?

 

No

 

No

 

No

 

Is the ignition knob turned 

on fully? (it must be turned 

to the big flame)

 

 

Yes

 

Yes

 

The remote control react 

well?

 

Check if the batteries in the 
transmitter and receiver are 

charged.

 

No

 

Yes

 

Yes

The TWIN burns very blue. 

(It needs ±30 minutes in 

order to heat up 

completely)

 

Check the flue connection: does 

this comply with Kal-Fire’s 

installation conditions?

 

Yes

 

No

 

Please contact your dealer 
about other problems

 

No

 

 

 
 

 

26

 

6.3

 

Solutions flowchart - TWIN radio 

 

 
 

 

 

Is ignition sparking?

 

 

Ignition sparks, does the 
pilot light go on?

 

Ignition sparks, and 
pilot light comes on, 
but does it also stay 
on?

 

Burner bed comes on

 

 

The TWIN burns very blue.

(It needs ±30 minutes in 

order to heat up 

completely)

 

 

Please contact your dealer 
about other problems

 

Does pilot light go out 
directly?

 

Is a red lamp alight (reset knob) on the gas 
control unit or does the fire not react? 

 

Can you hear a click when you press the 
remote control? 

 

Check that ignition cable is hanging free 
and not clamped against an iron 
component, or this sparks continuously.

 

There may be turbulence in the 
pilot light, which means it is being 
blown away. This could be 
because the chips are lying in 
front of the pilot light. Reposition 
them and try again

 

 

Check the flue connection: does 

this comply with Kal-Fire’s 

installation conditions?

 

 

Press this reset knob in or use the 
remote control (see chapter 4.3.1). At 
the beginning thismay occur because 
there is air in the gas supply pipe. 
Does this work? 

 

On the black box of the gas control unit is 
a large black knob, press this in 
simultaneously with the remote control 
knobs. This will synchronize the receiver 
and transmitter. Does this work? 

 

Check whether the distance between 
ionization pen and thermocouple is not too 
great to spark across. If  necessary, bend 
closer.

 

The gas control unit is phase-sensitive, so  
turn the plug round and check whether the 
electric socket is earthed and connected 
correctly, the earth is essential for proper 
operation, does this work? 

Yes

 

No

 

No

 

No

 

No

 

No

 

No

 

Yes

 

Yes

 

No

 

  Yes

 

No

 

No

 

Yes

 

No

 

No

 

    Yes

 

No

 

Yes 

 

Yes

 

No

 

Yes

 

Contact your dealer

 

.

Check whether the gas tap is open 
or that there is a blockage in the 
gas supply

 

Содержание TWIN 38x15

Страница 1: ...NTROL UNIT 7 2 6 ASSEMBLY OF THE RADIOGRAFIC GAS CONTROL UNIT 8 2 7 POSITIONING OF THE CHIPS AND LOGS 11 2 8 EXTRA ACCESOIRES 14 2 8 1 OPTIONAL SET OF LOGS 14 2 8 2 THE FLOORBURNER 14 3 TECHNICAL DATA 16 3 1 3 1 TWIN 38 15 16 3 2 3 2 TWIN 50 15 16 3 3 3 3 TWIN 80 15 16 4 OPERATING INSTRUCTIONS 17 4 1 MANUAL CONTROLLED APPLIANCES 17 4 1 1 LIGHTING THE BURNERS 17 4 1 2 EXTINGUISHING THE BURNERS 18 4...

Страница 2: ...RICAL CONNECTION WITH FAN 31 ANNEX 3 GRAFIC FOR CALCULATION FLUE DUCT 32 4 Inleiding The open gas log fire from the TWIN series of the brand KAL FIRE you have purchased is a product of which you will enjoy great pleasure in heating year after year We recommend checking the appliance at delivery for possible transport damage Carefully read the accompanying instructions before installing or taking t...

Страница 3: ...least 15 cm per kW maximum output Construction of a controlled flue gas regulator 6 Flue gasses have to be evacuated by means of a fan designed for flue gasses The appliance has to be equipped with a flow protection thermal shut off safety or oxistop A fan suitable for evacuation of flue gasses has to be used Kal Fire recommends the EXHAUSTO RSVG fans Inatherm 1 2 General requirements A The flue m...

Страница 4: ...he ultrasonic gas control unit The appliance is standardly delivered connected to the gas control unit and has to be connected to the gas tap not included as following Connect the gas supply 12 mm to the gas control unit 12 mm clamp Test leak tightness of the system by means of soapsuds or leakage testing spray Check the protection system by activating the security the appliance should go out 8 As...

Страница 5: ...connect an EXHAUSTO RSVG fan For this purpose the electrical layout has to be changed to the the plan in annex 2 An extra wire is include for this purpose and has to be connected as below Step 1 Remove plug 1 Step 2 Insert the delivered plug onto the cable tree Step 3 Connect the other four cables to the EFC 21 EFC 25 10 ATTENTION This receiver has tob e mounted outside of the burner s radiation a...

Страница 6: ...n place it is best to position the rearmost log first and also the two logs on either side The chips can then be laid on the logs There will then be plenty of air under these logs which will produce a better glow Tip 3 You may partly cover the pilot light cap but you must be able to see that the pilot light is burning at all times This will produce a more realistic effect Caution The chips must no...

Страница 7: ...ra accesoires 2 8 1 Optional set of logs For the TWIN 5015 extra accessoires can be ordered It is possible to order an optional set of logs This is the optional set of logs 2 8 2 The floorburner It is possible to built the gas log fire in a sunken casing An advantage of this is that it is included with a controlled air supply and a burner plate as a cover 1 3 2 4 5 ...

Страница 8: ... AT CH GB IT Propaan Type B11 B21 B11 B21 B11 B21 B11 B21 B11 B21 Gas P G20 20 mbar G20 20 mbar G25 25 mbar G25 25 mbar G25 20 mbar G20 20 mbar G30 37 mbar Gascat I2L I2E I2ELL I2H I3P Input 17 45 kW 18 38 kW 15 53 kW 15 17 kW Max min 2 14 0 73 m3 h 1 94 0 83 m3 h 1 92 0 78 m3 h 0 61 0 23 m3 h Branderdruk 23 8 mbar 18 8 mbar 19 0 mbar 36 7 mbar 18 38 kW 1 94 0 75 m3 h 18 8 mbar Model NL BE FR DE A...

Страница 9: ... in until the pilot light is burning steadily This can take longer straight after mounting because the gas pipe still has to fill with gas When the pilot light is burning keep the knob 1 pressed in for approximately another 20 seconds otherwise repeat the above operation 1 2 Figure 11 Manually controlled appliance 18 Now release the knob 1 If the pilot light does not keep burning wait for 3 minute...

Страница 10: ...e knob 3 If the pilot light does not keep burning wait for 3 minutes and then repeat the above steps Now turn the knob 3 fully in the opposite direction as far as the position with the big flame You can now adjust the height of the flames with the remote control Figure 13 For higher flames press in the top knob 6 and the left hand knob 8 simultaneously For lower flames press in the bottom knob 7 T...

Страница 11: ...inimum You can adjust the burners higher and lower with no 1 and no 2 Resetten the appliance If still no flame is detected after 30 seconds of sparking the automated burner unit safety lock will be activated You can reset the automatic burner unit by means of the remote control and or a reset knob on the automatic burner unit itself This procedure may have to be repeated several times when the app...

Страница 12: ...ng blown away This could be because the chips are lying in front of the pilot light Reposition them and try again Check whether the distance between ionization pen and thermocouple is not too great to spark across If necessary bend closer Nee No Ja Yes No Yes No Contact your dealer Check whether the gas tap is open or that there is a blockage in the gas supply No No Yes Yes Does the microswitch sh...

Страница 13: ... on Ignition sparks and pilot light comes on but does it also stay on Burner bed comes on The TWIN burns very blue It needs 30 minutes in order to heat up completely Please contact your dealer about other problems Does pilot light go out directly Is a red lamp alight reset knob on the gas control unit or does the fire not react Can you hear a click when you press the remote control Check that igni...

Страница 14: ... starting on the date of purchase which must be clearly and distinctly stated on the sales invoice The attached warranty registration card should be carefully completed and returned to Kal Fire B V 3 The warranty does not cover the ceramic glass or external physical and chemical effects during transit storage or assembly 4 If a problem should however occur within the warranty period due to a manuf...

Страница 15: ...ed or different ones are placed on the burner bed 7 If this warranty certificate together with the original dated proof of purchase cannot be produced likewise if it appears that the details in this proof of purchase have been manipulated date deleted made illegible changed etc 30 Annex 1 Outlet area s Schuin dak Dakhelling 23 Plat dak Schuin dak Dakhelling 23 I I III III 0 5 m 0 5 m 0 8 m I Flat ...

Страница 16: ...e buttons High en X 2 1 TTB 230V Inatherm Chimney Fan Fan dP Pressure differential NO NC C L Nre PE Inatherm EFC21 L N PE 8 9 10 11 12 13 14 15 POWER 2 1 GNYE START IN AIR INLET RELEASE OUT STEP 2 OUT 1 2 3 4 5 P D S F A N 6 7 S M G X1 1 11 X1 2 1 8 9 11 4 13 Earth to gasregulator 2 1 GNYE L N GND Power Earthing Phase terminal Y1 Y2 32 Annex 3 Grafic for calculation flue duct 0 2 0 3 0 4 0 5 0 6 0...

Отзывы: