You can configure Parity to be odd, even, or none by selecting from the drop 
down menu in the Kaiterra Configuration Tool. The default setting for Parity is 
“even”.

 

 

If your Modbus network does not use parity checking, select “none”. Please 
consult your Modbus network admin or BMS admin to confirm the parity type of 
your local network. Please note that all devices in the same network should be set 
to the same parity type.

 

 

Setting AQI 

You can choose your AQI standard and customize your AQI calculation in the 
Kaiterra Configuration Tool. AQI stands for Air Quality Index, an index calculated 
based on the concentration of a set of air pollutants. Sensedge Mini o

ff

ers AQI 

value in the Modbus communication so that you can integrate the information 
into your local system. 

Choose the AQI standard from the drop down menu in the Kaiterra Configuration 
Tool, and select the pollutants used for the AQI calculation. Please note that only 
the pollutants monitored by your device can be included in the calculation. 

Please consult the facility manager or other responsible personnel if the Modbus 
address is not clear. 

Click save and disconnect your computer from the “Kaiterra” network. 

Содержание Sensedge Mini

Страница 1: ...KAITERRA www kaiterra com Kaiterra Sensedge Mini Modbus User Manual JULY 2020...

Страница 2: ...rnet as its wiring type Modbus supports communication to and from multiple devices connected to the same cable or Ethernet network Sensedge Mini provides Modbus RTU support via the RS 485 port on the...

Страница 3: ...bles through the opening on the plate and plug the 4 pin Phoenix pin plug into the corresponding terminals on the back of the device The default Modbus address is set as 1 and can be changed later via...

Страница 4: ...on history page later on to help you quickly connect the device to the Kaiterra dashboard Enter the Modbus settings details to the applicable fields on the Configuration Tool following the instruction...

Страница 5: ...ize your AQI calculation in the Kaiterra Configuration Tool AQI stands for Air Quality Index an index calculated based on the concentration of a set of air pollutants Sensedge Mini offers AQI value in...

Страница 6: ...ands 1 Read Input Register 0x04 command 01 04 00 00 00 05 30 09 to read all input register 2 Write single Register 0x06 command 01 06 00 00 00 02 08 0B to set the modbus address to 0x02 3 Read holding...

Страница 7: ...0 Input register 3 Humidity R 0 0 100 RH Input register 4 CO2 R 0 9999 ppm Input register 5 PM10 R 0 999 ug m3 Input register 6 HCHO R 0 2000 ppb Input register 7 CO R 0 0 500 0 ppm Input register 8 O...

Страница 8: ...erature T k 273 15 t celsius Temperature and humidity have resolution of 0 1 the transmitted data is 10 times of the raw data Holding Register 0 Modbus address code R W Min 1 Max 247 Holding Register...