Setting Modbus on Sensedge Mini 

A. Set up Modbus via RS-485 

To set up Modbus communication, connect your cable from the RS-485 network to a 
4-pin Phoenix pin plug. Check the “A” “B” marks on the back of the device to make 
sure the cables are connected in the right order, and fasten the screws on the 
Phoenix pin plug to secure the cables. 

Run the cables through the opening on the plate, and plug the 4-pin Phoenix pin 
plug into the corresponding terminals on the back of the device. 

The default Modbus address is set as 1, and can be changed later via the Kaiterra 
Configuration Tool. 

B. Prepare for Configuration 

Download the Kaiterra Configuration Tool and install it on your computer.

 

 

After the device has been turned on, it will automatically enter the configuration 
mode for 15 minutes. The STATUS light will flash in yellow. If your device isn’t in 
configuration mode, please turn o

ff

 the device and turn it back on again. 

Содержание Sensedge Mini

Страница 1: ...KAITERRA www kaiterra com Kaiterra Sensedge Mini Modbus User Manual JULY 2020...

Страница 2: ...rnet as its wiring type Modbus supports communication to and from multiple devices connected to the same cable or Ethernet network Sensedge Mini provides Modbus RTU support via the RS 485 port on the...

Страница 3: ...bles through the opening on the plate and plug the 4 pin Phoenix pin plug into the corresponding terminals on the back of the device The default Modbus address is set as 1 and can be changed later via...

Страница 4: ...on history page later on to help you quickly connect the device to the Kaiterra dashboard Enter the Modbus settings details to the applicable fields on the Configuration Tool following the instruction...

Страница 5: ...ize your AQI calculation in the Kaiterra Configuration Tool AQI stands for Air Quality Index an index calculated based on the concentration of a set of air pollutants Sensedge Mini offers AQI value in...

Страница 6: ...ands 1 Read Input Register 0x04 command 01 04 00 00 00 05 30 09 to read all input register 2 Write single Register 0x06 command 01 06 00 00 00 02 08 0B to set the modbus address to 0x02 3 Read holding...

Страница 7: ...0 Input register 3 Humidity R 0 0 100 RH Input register 4 CO2 R 0 9999 ppm Input register 5 PM10 R 0 999 ug m3 Input register 6 HCHO R 0 2000 ppb Input register 7 CO R 0 0 500 0 ppm Input register 8 O...

Страница 8: ...erature T k 273 15 t celsius Temperature and humidity have resolution of 0 1 the transmitted data is 10 times of the raw data Holding Register 0 Modbus address code R W Min 1 Max 247 Holding Register...