C.  Connect to Network 

Open network settings on your computer and look for the Wi-Fi network that starts 
with “Kaiterra”. Connect your computer to that network. Click “Identify device” to 
identify the device currently being configured if multiple devices are present. The 
STATUS light will flash yellow rapidly for about 5 seconds. 

On the Configuration Tool, you can enter a name for the device (e.g. the location of 
the device or the serial number) and a project tag. This will provide easy 
identification and filtering in the configuration history page later on to help you 
quickly connect the device to the Kaiterra dashboard. 

Enter the Modbus settings details to the applicable fields on the Configuration Tool 
following the instructions below: 

Setting Device Address 

You can customize your device address in the Kaiterra Configuration Tool. The 
device address is used to identify the device in the system, so please make sure 
each device is given a unique device address. 

Customize your device address by entering an address from 1 to 247 in the 
address field in the Kaiterra Configuration Tool. It’s recommended to set your 
device address onsite during or right after installation, so that you can keep track 
of the device installed and the corresponding device address. 

Setting Parity Type 

Содержание Sensedge Mini

Страница 1: ...KAITERRA www kaiterra com Kaiterra Sensedge Mini Modbus User Manual JULY 2020...

Страница 2: ...rnet as its wiring type Modbus supports communication to and from multiple devices connected to the same cable or Ethernet network Sensedge Mini provides Modbus RTU support via the RS 485 port on the...

Страница 3: ...bles through the opening on the plate and plug the 4 pin Phoenix pin plug into the corresponding terminals on the back of the device The default Modbus address is set as 1 and can be changed later via...

Страница 4: ...on history page later on to help you quickly connect the device to the Kaiterra dashboard Enter the Modbus settings details to the applicable fields on the Configuration Tool following the instruction...

Страница 5: ...ize your AQI calculation in the Kaiterra Configuration Tool AQI stands for Air Quality Index an index calculated based on the concentration of a set of air pollutants Sensedge Mini offers AQI value in...

Страница 6: ...ands 1 Read Input Register 0x04 command 01 04 00 00 00 05 30 09 to read all input register 2 Write single Register 0x06 command 01 06 00 00 00 02 08 0B to set the modbus address to 0x02 3 Read holding...

Страница 7: ...0 Input register 3 Humidity R 0 0 100 RH Input register 4 CO2 R 0 9999 ppm Input register 5 PM10 R 0 999 ug m3 Input register 6 HCHO R 0 2000 ppb Input register 7 CO R 0 0 500 0 ppm Input register 8 O...

Страница 8: ...erature T k 273 15 t celsius Temperature and humidity have resolution of 0 1 the transmitted data is 10 times of the raw data Holding Register 0 Modbus address code R W Min 1 Max 247 Holding Register...