When a safety device is activated, an error code will be displayed on the user interface.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
In case this procedure for resetting the safety is not successful, contact your local dealer.
13.4 Error codes
The power consumption parameter is preparatory. some parameter is not be activated in the system, the parameter will
show "--"
The heat pump capacity is for reference only, not used to judge the ability of the unit. The accuracy of sensor is ±1
℃
.
The flow rates parameters are calculated according to the pump running parameters,the deviation is different at different flow
rates,the maximum of deviation is 25%.
NOTE
OPERATION PARAMETER
#01
IDU TARGET FREQUENCY 46Hz
ADDRESS
FREQUENCY LIMITED TYPE 5
FAN SPEED 600R/MIN
SUPPLY VOLTAGE 230V
DC GENERATRIX VOLTAGE 420V
DC GENERATRIX CURRENT 18A
7/9
OPERATION PARAMETER
#01
TW_I PLATE W-INLET TEMP. 30°C
ADDRESS
T2 PLATE F-OUT TEMP. 35°C
TW_O PLATE W-OUTLET TEMP. 35°C
T2B PLATE F-IN TEMP. 35°C
Th COMP. SUCTION TEMP. 5°C
Th COMP. DISCHARGE TEMP. 75°C
8/9
OPERATION PARAMETER
#01
T4 OUTDOOR AIR TEMP. 5°C
ADDRESS
TF MODULE TEMP. 55°C
T3 OUTDOOR EXCHARGE TEMP. 5°C
P1 COMP. PRESSURE 2300kPa
ODU SOFTWARE 01-09-2018V01
HMI SOFTWARE 01-09-2018V01
9/9
ERROR
CODE
MALFUNCTION
OR PROTECTION
FAILURE CAUSE
AND CORRECTIVE ACTION
Water flow fault (E8
displayed 3 times)
1.The wire circuit is short connected or open. Reconnect the wire
correctly.
2.Water flow rate is too low.
3. Water flow switch is failed, switch is open or close continuously,
change the water flow switch.
Phase loss or neutral wire and
live wire are connected
reversely
1.Check the power supply cables should be connected stable, to avoid
phase loss.
2.Check the power supply cables sequence, change any two cables
sequence of the three power supply cables.
Communication fault between
controller and main control
board of hydraulic module
’
1.The wire doesn’t connect between wired controller and unit. connect
the wire.
2.Communication wire sequence is not right. Reconnect the wire in
the right sequence.
3. Whether there is a high magnetic field or high power interfere, such
as lifts, large power transformers, etc..
4. To add a barrier to protect the unit or to move the unit to the other
place.
Final outlet water temp. sensor
(T1) fault.
1. Check the resistance of the sensor
2. The T1 sensor connector is loosen. Reconnect it.
3.The T1 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive.
4.The T1 sensor failure, change a new sensor.
Water tank temp. sensor
(T5) fault.
1. Check the resistance of the sensor
2.The T5 sensor connector is loosen. Reconnect it.
3.The T5 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4.The T5 sensor failure, change a new sensor
62
ERROR
CODE
MALFUNCTION
OR PROTECTION
FAILURE CAUSE
AND CORRECTIVE ACTION
The condenser outlet
refrigerant temperature sensor
(T3) fault.
1. Check the resistance of the sensor
2. The T3 sensor connector is loosen. Reconnect it.
3.The T3 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The T3 sensor failure, change a new sensor.
The ambient temperature
sensor (T4) fault.
1. Check the resistance of the sensor
2. The T4 sensor connector is loosen. Reconnect it.
3.The T4 sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The T4 sensor failure, change a new sensor.
The balance tank up temp.
sensor (Tbt1) fault.
1.Check the resistance of the sensor.
2.The Tbt1 sensor connector is loosen,reconnect it.
3.The Tbt1 sensor connector is wet or there is water in,remove the
water ,make the connector dry.Add waterproof adhesive.
4.The Tbt1 sensor failure,change a new sensor.
Water flow fault.
Check that all shut off valves of the water circuit are completely open.
1. Check if the water filter needs cleaning.
2. Refer to "9.4 Charging water"
3. Make sure there is no air in the system(purge air).
4. Check on the manometer that there is sufficient water pressure. The
water pressure must be >1 bar.
5. Check that the pump speed setting is on the highest speed.
6. Make sure that the expansion vessel is not broken.
7. Check that the resistance in the water circuit is not too high for the
pump (refer to "Setting the pump speed" ).
8. If this error occurs at defrost operation (during space heating or
domestic water heating), make sure that the backup heater power
supply is wired correctly and that fuses are not blown.
9. Check that the pump fuse and PCB fuse are not blown.
Compressor suction temp.
sensor (Th) fault.
1.Check the resistance of the sensor.
2. The Th sensor connector is loosen. Reconnect it.
3.The Th sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The Th sensor failure, change a new sensor.
Compressor discharge temp.
sensor (Tp) fault.
1.Check the resistance of the sensor.
2. The Tp sensor connector is loosen. Reconnect it.
3.The Tp sensor connector is wet or there is water in. remove
the water, make the connector dry. Add waterproof adhesive
4. The Tp sensor failure, change a new sensor.
Solar panel temp.sensor
(Tsolar) fault.
1.Check the resistance of the sensor.
2.The Tsolar sensor connector is loosen,reconnect it.
3.The Tsolar sensor connector is wet or there is water in,remove the
water ,make the connector dry.Add waterproof adhesive.
4.The Tsolar sensor failure,change a new sensor.
145
144