57
Before switching on the unit, read following recommenda-
tions:
The installer is obliged to verify correct operation of unit
after installation.
11 TEST RUN AND FINAL
CHECKS
11.1 Final checks
When the complete installation and all necessary
settings have been carried out, close all front panels
of the unit and refit the unit cover.
The service panel of the switch box may only be
opened by a licensed electrician for
If required, the installer can perform a manual test run
operation at any time to check correct operation of air
purge, heating, cooling and domestic water heating, refer
to 10.7 Field settings/test run.
11.2 Test run operation (manually)
That during the first running period of the unit,
required power input may be higher than stated
on the nameplate of the unit. This phenomenon
originates from the compressor that needs
elapse of a 50 hours run in period before
reaching smooth operation and stable power
consumption.
NOTE
In order to ensure optimal availability of the unit, a number
of checks and inspections on the unit and the field wiring
have to be carried out at regular intervals.
This maintenance needs to be carried out by your local
technician.
In order to ensure optimal availability of the unit, a number
of checks and inspections on the unit and the field wiring
have to be carried out at regular intervals.
This maintenance has to be carried out by your local
technician.
12 MAINTENANCE AND
SERVICE
DANGER
ELECTRIC SHOCK
Before carrying out any maintenance or
repairing activity, must switch off the power
supply on the supply panel.
Do not touch any live part for 10 minutes after
the power supply is turned off.
The crank heater of compressor may operate
even in standby.
Please note that some sections of the electric
component box are hot.
Forbid touch any conductive parts.
Forbid rinse the unit. It may cause electric
shock or fire.
Forbid leave the unit unattended when
service panel is removed.
Make sure that the disposal of the glycol solution is done
in accordance with relevant local laws and regulations.
Water pressure
Check the water pressure, if it is below 1 bar,fill water
to the system.
Water filter
Clean the water filter.
Water pressure relief valve
Check for correct operation of the pressure relief
valve by turning the black knob on the valve
counter-clockWise:
-If you do not hear a clacking sound, contact your
local dealer.
-In case the water keeps running out of the unit, close
both the water inlet and outlet shut-off valves first and
then contact your local dealer.
Pressure relief valve hose
Check that the pressure relief valve hose is
positioned appropriately to drain the water.
Backup heater vessel insulation cover
Check that the backup heater insulation cover is
fastened tightly around the backup heater vessel.
Domestic hot water tank pressure relief valve (field
supply) Applies only to installations with a domestic
hot water tank. Check for correct operation of the
pressure relief valve on the domestic hot water tank.
Domestic hot water tank booster heater
Applies only to installations with a domestic hot water
tank. It is advisable to remove lime buildup on the
booster heater to extend its life span, especially in
regions with hard water. To do so, drain the domestic
hot water tank, remove the booster heater from the
domestic hot water tank and immerse in a bucket (or
similar) with lime-removing product for 24 hours.
Unit switch box
-Carry out a thorough visual inspection of the switch
box and look for obvious defects such as loose
connections or defective wiring.
-Check for correct operation of contactors with an
ohm meter. All contacts of these contactors must be
in open position.
Use of glycol (Refer to 9.3 Water pipework Caution:
"Use of glycol" ) Document the glycol concentration
and the pH-value in the system at least once a year.
-A PH-value below 8.0 indicates that a significant
portion of the inhibitor has been depleted and that
more inhibitor needs to be added.
-When the PH-value is below 7.0 then oxidation of the
glycol occurred, the system should be drained and
flushed thoroughly before severe damage occurs.
The following checks must be performed at least once a
year by qualified person.
58
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no
circumstances can safety devices be bridged or changed to a value other than the factory setting. If the cause of the problem
cannot be found, call your local dealer.
If the pressure relief valve is not working correctly and is to be replaced, always reconnect the flexible hose attached to the
pressure relief valve to avoid water dripping out of the unit!
Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects
such as loose connections or defective wiring.
For problems related to the optional solar kit for domestic water heating, refer to the troubleshooting in the Installation
& Owner's manual for that kit.
NOTE
When carrying out an inspection on the switch box of the unit, always make sure that the main switch of the unit is
switched off.
WARNING
This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be carried out by your local technician.
13 TROUBLE SHOOTING
13.1 General guidelines
Symptom 2: The unit is turned on but the compressor is not starting (space heating or domestic water heating)
POSSIBLE CAUSES
CORRECTIVE ACTION
The unit must start up
out of its operation range
(the water temperature
is too low).
In case of low water temperature, the system utilizes the backup heater to
reach the minimum water temperature
first (12°C).
• Check that the backup heater power supply is correct.
• Check that the backup heater thermal fuse is closed.
• Check that the backup heater thermal protector is not activated.
• Check that the backup heater contactors are not broken.
Symptom 1: The unit is turned on but the unit is not heating or cooling as expected
13.2 General symptoms
POSSIBLE CAUSES
CORRECTIVE ACTION
The temperature setting
is not correct.
Check the controller set point.T4HMAX,T4HMIN in heat mode.
T4CMAX,T4CMIN in cool mode.T4DHWMAX,T4DHWMIN
in DHW mode.
The water flow is too low.
• Check that all shut off valves of the water circuit are
completely open.
• Check if the water filter needs cleaning.
• Make sure there is no air in the system (purge air).
• Check on the manometer that there is sufficient water pressure.
The water pressure must be>1 bar (water is cold).
• Make sure that the expansion vessel is not broken.
• Check that the resistance in the water circuit is not too high
for the pump.
The water volume in the
installation is too low.
Make sure that the water volume in the installation is above
the minimum required value (refer to "9.3 water piping/
Checking the water volume and expansion vessel pre-pressure").
141
140