MLCAC-UTSM-2010-10
Precaution on Installation
Installation
125
1. Precaution on Installation
1). Measure the necessary length of the connecting pipe, and make it by the following way.
a.
Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
Specially Notice the pipe length/height/dimension of each capacity.
Maximum pipe length
Model
Max. Length
Max. Elevation
12,000Btu/h
10m
5m
18,000Btu/h ~24,000Btu/h
25m
12m
30,000Btu/h
25m
15m
36,000Btu/h
30m
20m
48,000Btu/h~60,000Btu/h
50m
25m
Piping sizes
Model
Liquid(mm)
Gas(mm)
12,000Btu/h~18,000Btu/h
6.4
12.7
24,000Btu/h~60,000Btu/h
9.5
15.9
CAUTIONS
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Flare dimension A
Min (mm) Max
Flare shape
Φ6.4
14.2
~
17.2N.m
(144
~
176 kgf.cm)
8.3
8.7
Φ9.5
32.7
~
39.9N.m
(333
~
407kgf.cm)
12.0
12.4
Φ12.7
49.5
~
60.3N.m
(504
~
616kgf.cm)
15.4
15.8
Φ15.9
61.8
~
75.4N.m
(630
~
770 kgf.cm)
18.6
19.1
Φ19.1
97.2
~
118.6N.m
(990
~
1210kgf.cm)
22.9
23.3
b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part
of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other
impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
c.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
2) Locate The Pipe
a.
Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover.
b.
Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by
condensation.
c.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.
3) Connect the pipes.
4) Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in
fluent flow.
5) Be sure of no leakage by checking it with leak detector or soap water.
6) Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to
prevent leakage.
Содержание KOU-12HDN1
Страница 1: ...Service Manual 2010...
Страница 2: ......
Страница 4: ......
Страница 15: ...MLCAC UTSM 2010 10 Dimensions New Four way Cassette Compact 11 3 Dimensions 4 Service Space...
Страница 20: ...Field Wiring MLCAC UTSM 2010 10 16 New Four way Cassette Compact 11 Field Wiring KCA2 12HRDN1 Q KCA2 18HRDN1 Q...
Страница 21: ...MLCAC UTSM 2010 10 Field Wiring New Four way Cassette Compact 17 KCA2 12HRDN1 Q KCA2 18HRDN1 Q...
Страница 30: ...Service Space MLCAC UTSM 2010 10 26 Four way Cassette Type 4 Service Space For 18 48k For 60k...
Страница 36: ...The Specification of Power MLCAC UTSM 2010 10 32 Four way Cassette Type 10 The Specification of Power...
Страница 37: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 33 11 Field Wiring Wiring chart...
Страница 38: ...Field Wiring MLCAC UTSM 2010 10 34 Four way Cassette Type...
Страница 52: ...The Specification of Power MLCAC UTSM 2010 10 48 Duct Type 10 The Specification of Power...
Страница 53: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 49 11 Field Wiring...
Страница 54: ...Field Wiring MLCAC UTSM 2010 10 50 Duct Type Air conditioner link circuit...
Страница 55: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 51...
Страница 56: ...Field Wiring MLCAC UTSM 2010 10 52 Duct Type...
Страница 64: ...Service Space MLCAC UTSM 2010 10 60 Ceiling Floor Type 4 Service Space...
Страница 65: ...MLCAC UTSM 2010 10 Wiring Diagrams Ceiling Floor Type 61 5 Wiring Diagrams KUB 12HRDN1...
Страница 72: ...The Specification of Power MLCAC UTSM 2010 10 68 Ceiling Floor Type 10 The Specification of Power...
Страница 73: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 69 11 Field Wiring...
Страница 74: ...Field Wiring MLCAC UTSM 2010 10 70 Ceiling Floor Type...
Страница 75: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 71...
Страница 79: ...MLCAC UTSM 2010 10 Dimensions Console Type 75 3 Dimensions KFA 12HRDN1 KFA 18HRDN1...
Страница 80: ...Service Space MLCAC UTSM 2010 10 76 Console Type 4 Service Space...
Страница 86: ...The Specification of Power MLCAC UTSM 2010 10 82 Console Type 10 The Specification of Power...
Страница 87: ...MLCAC UTSM 2010 10 Field Wiring Console Type 83 11 Field Wiring...
Страница 88: ...Field Wiring MLCAC UTSM 2010 10 84 Console Type...
Страница 89: ......
Страница 97: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 93 3 Service Space...
Страница 99: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 95 5 Wiring Diagrams KOU 12HDN1...
Страница 100: ...Wiring Diagrams MLCAC UTSM 2010 10 96 Outdoor Units KOUA 18HDN1 C0 KOUB 24HDN1...
Страница 101: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 97 KOU 30HDN1 KOU 36HDN1 KOU 48HDN1...
Страница 102: ...Wiring Diagrams MLCAC UTSM 2010 10 98 Outdoor Units KOUB 36HDN1 R KOUB 48HDN1 R KOUA 60HRDN1...
Страница 103: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 99 KOUD 60HDN1 R...
Страница 110: ...Troubleshooting MLCAC UTSM 2010 10 106 Outdoor Units...
Страница 139: ...MLCAC UTSM 2010 10 Control Control 135 Part 5 Control 1 Wireless Remote Controller 136...