07
NOTE
About Fluorinated Gases
- This air-conditioning unit contains fluorinated gases. For specific information on the type of gas and the amount,
please refer to the relevant label on the unit itself. Compliance with national gas regulations shall be observed.
- Installation, service, maintenance and repair of this unit must be performed by a certified technician.
- Product uninstallation and recycling must be performed by a certified technician.
- If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months. When
the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.
Install the power wire at least 3 feet (1 meter) away from televisions or radios to prevent interference or noise.
(Depending on the radio waves, a distance of 3 feet (1 meter) may not be sufficient to eliminate the noise.)
Do not wash the unit. This may cause electric shocks or fire. The appliance must be installed in accordance with
national wiring regulations. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent
or similarly qualified persons in order to avoid a hazard.
Do not install the unit in the following places:
- Where there is mist of mineral oil, oil spray or vapors. Plastic parts may deteriorate, and cause them to come loose
or water to leak.
- Where corrosive gases (such as sulphurous acid gas) are produced. Where corrosion of copper pipes or soldered
parts may cause refrigerant to leak.
- Where there is machinery which emits electromagnetic waves. Electromagnetic waves can disturb the control
system and cause equipment malfunction.
- Where flammable gases may leak, where carbon fiber or ignitable dust is suspended in the air or where volatile
flammables such as paint thinner or gasoline are handled. These types of gases might cause a fire.
- Where the air contains high levels of salt such as near the ocean.
- Where voltage fluctuates a lot, such as in factories.
- In vehicles or vessels.
- Where acidic or alkaline vapors are present.
This appliance can be used by children 8 years old and above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they are supervised or given instruction on using the unit in a
safe manner and understand the hazards involved. Children should not play with the unit. Cleaning and user
maintenance should not be done by children without supervision.
Children should be supervised to ensure that they do not play with the appliance.
If the supply cord is damaged, it must be replaced by the manufaturer or its service agent or a similarly qualified
person.
DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste seperatelly for
special treatment is necessary. Do not dispose of electrical appliances as municipal waste, use seperate collection
facilities. Contact your local goverment for information regarding the collection systems available. If electrical
appliances are disposed of in landfills or dumps, hazardous substance can leak into the groudwater and get into the
food chain, damaging your health and well-being.
The wiring must be performed by certified person technicians in accordance with national wiring regulation and this
circuit diagram. An all-pole disconnection device which has at least 3mm seperation distance in all pole and a
residualcurrent device(RCD) with the rating not exceeding 30mA shall be incorporated in the fixed wiring according
to the national rule.
Confirm the safety of the installation area ( walls, floors, etc. ) without hidden dangers such as water, electricity, and
gas before wiring/pipes.
Before installation , check whether the user's power supply meets the electrical installation requirements of unit (
including reliable grounding , leakage , and wire diameter electrical load, etc. ). If the electrical installation
requirements of the product are not met, the installation of the product is prohibited until the product is rectified.
Product installation should be fixed firmly, Take reinforcement measures, when necessary.
CAUTION
Before installation
Be sure to confirm the model name and the serial number of the unit.
2 BEFORE INSTALLATION
08
Frequency of Refrigerant Leakage Checks
- For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO
2
equivalent or more,but of less than
50 tonnes of CO
2
equivalent,at least every 12 months, or where a leakage detection system is installed, at least every 24
months.
- For unit that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO
2
equivalent or more, but of less
than 500 tonnes of CO
2
equivalentat least every six months, or where a leakage detection system is installed, at least
every 12 months.
- For unit that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO
2
equivalent or more,at least every
three months, or where a leakage detection system is installed,at least every six months.
- This air-conditioning unit is a hermetically sealed equipment that contains fluorinated greenhouse gases.
- Only certificated person is allowed to do installation, operation and maintenance.
CAUTION
3 INSTALLATION SITE
There is flammable refrigerant in the unit and it should be installed in a well-ventilated site. If the unit is installed inside,
an additional refrigerant detection device and ventilation equipment must be added in accordance with the standard
EN378. Be sure to adopt adequate measures to prevent the unit from being used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunction, smoke or fire. Please instruct the customer
to keep the area around the unit clean.
WARNING
Select an installation site where the following conditions are satisfied and one that meets with your customer's approval.
- Places that are well-ventilated.
- Safe places which can bear the unit's weight and vibration and where the unit can be installed at an even level.
- Places where there is no possibility of flammable gas or product leak.
- The equipment is not intended for use in a potentially explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the units' piping and wiring lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause damage to the location (e.g. in case of a blocked drain pipe).
- Do not install the unit in places often used as a work space. In case of construction work (e.g. grinding etc.) where a lot of
dust is created, the unit must be covered.
- Do not place any object or equipment on top of the unit (top plate)
- Do not climb, sit or stand on top of the unit.
- Be sure that sufficient precautions are taken in case of refrigerant leakage according to relevant local laws and regulations.
The equipment is not intended for use in a potentially explosive atmosphere.