Safety 

Precautions

 Page 6

 WARNINGS FOR PRODUCT INSTALLATION

1.

 

Installation must be performed by an authorized dealer or specialist. Defective installation can 

cause water leakage, electrical shock, or fire. 

2.

 

Installation must be performed according to the installation instructions. Improper installation  

can cause water leakage, electrical shock, or fire. 

(

In North America,installation must be performed in accordance with the requirement of NEC  

and CEC by authorized personnel only.)

3.

 

Contact an authorized service technician for repair or maintenance of this unit. This appliance 

shall be installed in accordance with national wiring regulations.

4.

 

Only use the included accessories, parts, and specified parts for installation. Using non-standard 

parts can cause water leakage, electrical shock, fire, and can cause the unit to fail. 

5.

6.

 

Install the unit in a firm location that can support the unit’s weight. If the chosen location cannot 

support the unit’s weight, or the installation is not done properly, the unit may drop and cause 

serious injury and damage.

7.

8.

9.

10.

11.

Do not turn on the power until all work has been completed.

When moving or relocating the air conditioner, consult experienced service technicians for 

disconnection and reinstallation of the unit.

How to install the appliance to its support, please read the information for details in "indoor unit 

installation" and "outdoor unit installation" sections .

    

For units that have an auxiliary electric heater, 

do not 

install the unit within 1 meter (3 feet) of   

any combustible materials. 

  

Do not

 install the unit in a location that may be exposed to combustible gas leaks. If  

combustible gas accumulates around the unit, it may cause fire.

    

Install drainage piping according to the instructions in this manual. Improper drainage may 

cause water damage to your home and property. 

   

Note about Fluorinated Gasses(Not applicable to the unit using R290 Refrigerant)

1.    

This air-conditioning unit contains fluorinated greenhouse gasses. For specific information on the 

type of gas and the amount, please refer to the relevant label on the unit itself or 

the

 “Owner's Manual - Product Fiche ” in the packaging of the outdoor unit. 

(European 

Union products only)

.  

2.

   

Installation, service, maintenance and repair of this unit must be performed by a certified 

technician. 

3.

 

Product uninstallation and recycling must be performed by a certified technician.

4.    

For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO

2

 

equivalent or more, but of less than 50 tonnes of CO

2

 equivalent, If the system has a leak-

detection system installed, it must be checked for leaks at least every 24 months. 

5.

   

When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.

Содержание KFAU-12HRG32X

Страница 1: ...before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer inform...

Страница 2: ......

Страница 3: ...Drill wall hole for connective piping 6 Connect drain hose Outdoor Unit Installation 1 Select installation location 2 Install drain joint Wiring 1 Outdoor Uint Wiring 3 Power Specifications 3 Anchor o...

Страница 4: ...mell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into the air inlet or o...

Страница 5: ...nsion cord to power the unit Do not share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an al...

Страница 6: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 7: ...usable mechanical connectors and flared joints are not allowed indoors EN Standard Requirements Mechanical connectors used indoors shall have a rate of not more than 3g year at 25 of the maximum allow...

Страница 8: ...n buying a new appliance the retailer will take back the old appliance free of charge The manufacturer will take back the old appliance free of charge Sell the appliance to certified scrap metal deale...

Страница 9: ...ies Drain hose Refrigerant connecting pipe Display panel Air inlet with air filter in it Air flow louver at air outlet Air flow louver at air outlet Display panel Displays temperature and Error codes...

Страница 10: ...erature 16 C 32 C 60 F 90 F 0 C 30 C 32 F 86 F 10 C 32 C 50 F 90 F Outdoor Temperature 18 C 43 C 64 F 109 F 7 C 24 C 19 F 75 F 11 C 43 C 52 F 109 F 7 C 43 C 19 F 109 F For models with low temp cooling...

Страница 11: ...restart using the same settings Louver Angle Memory Function some models Some models are designed with a louver angle memory function When the unit restarts after a power failure the angle of the hor...

Страница 12: ...the switch status of the lower air louver on open of closed Page 12 Unit Specifications and Features Adjusting Air Flow Direction CAUTION Do not try to adjust the horizontal louver by hand This may ca...

Страница 13: ...to clean the filter once every two weeks WARNING DO NOT REMOVE OR CLEAN THE FILTER BY YOURSELF Removing and cleaning the filter can be dangerous Removal and maintenance must be performed by a certifie...

Страница 14: ...uthorized dealer or a licensed service provider Any unit repairs should be performed by an authorized dealer or a licensed service provider Maintenance Pre Season Inspection After long periods of non...

Страница 15: ...due to expansion and contraction of the unit s plastic parts Both the indoor unit and outdoor unit make noises Low hissing sound during operation This is normal and is caused by refrigerant gas flowin...

Страница 16: ...detailed description of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Caus...

Страница 17: ...mely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for l...

Страница 18: ...dels 2 1 Red short connected wire some models Air freshening filter some models The air conditioning system comes with the following accessories Use all of the installation parts and accessories to in...

Страница 19: ...Install the outdoor unit 1 2 3 4 5 MC MC 6 7 Install the indoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Perform a test run Page 19 Installation Summary...

Страница 20: ...accordance with the requirement of local and national standards The installation may be slightly different in different areas Unit Parts Display panel Drain pipe Connecting pipe Air inlet Air outlet A...

Страница 21: ...h room exists for installation and maintenance Enough room exists for the connecting the pipe and drainpipe The ceiling is horizontal and its structure can sustain the weight of the indoor unit The ai...

Страница 22: ...installed horizontally NOTE If the pipe comes out on the left it is necessary to loosen the screws on the bottom mounting plate If the pipe comes out in other directions it is not necessary Mounting p...

Страница 23: ...ounting plate installation Installation without skirting Installation with skirting line Knock the bottom mounting plate straight with a tool and fix it on the skirting line Two buckles The bottom mou...

Страница 24: ...and other sensitive Wall Indoor Outdoor 12mm 0 5 inch 2 Remove the cover plate NOTE All the figures in this manual are for demonstration purposes only The air conditioner you have purchased may be sli...

Страница 25: ...el switch malfunction In HEAT mode the outdoor unit will discharge water Ensure that the drain hose is placed in an appropriate area to avoid water damage and slippage DO NOT pull the drainpipe forcef...

Страница 26: ...ir outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong win...

Страница 27: ...ee Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to red...

Страница 28: ...6 14 673 26 5 403 15 87 952x1333x410 37 5x52 5x16 14 634 24 96 404 15 9 890x673x342 35x26 5x13 46 663 26 1 354 13 94 952x1333x415 37 5x52 5x16 34 634 24 96 404 15 9 845x702x363 33 27x27 6x14 3 540 21...

Страница 29: ...s meets the requirements shown in the following table The Maximum Length And Drop Height Based on Models Unit m ft Type of model Capacity Btu h Length of piping Maximum drop height North America Austr...

Страница 30: ...arped 90 DO NOT DEFORM PIPE WHILE CUTTING Be extra careful not to damage dent or deform the pipe while cutting This will drastically reduce the heating efficiency of the unit Step 2 Remove burrs Burrs...

Страница 31: ...Flare the pipe in accordance with the dimensions PIPING EXTENSION BEYOND FLARE FORM 8 Remove the flaring tool and flare form then inspect the end of the pipe for cracks and even flaring Step 4 Connect...

Страница 32: ...m 3 9 6 After connecting the copper pipes to the indoor unit wrap the power cable signal cable and the piping together with binding tape NOTE DO NOT intertwine signal cable with other wires While bund...

Страница 33: ...o the same power circuit 16 Connect the outdoor wires before connecting the indoor wires 7 Only connect the unit to an individual branch circuit outlet Do not connect another appliance to that outlet...

Страница 34: ...ased seperately purchased seperately Indoor unit power wires Indoor Outdoor connective wires Outdoor unit power wires C NOTE The cographs are for explanation purpose only Your machine may be slightly...

Страница 35: ...es 2 Pull the left and right handles of the front panel pull the panel outward and open the panel Magnetic ring if supplied and packed with the accessories Pass the belt through the hole of the Magnet...

Страница 36: ...FUSE A INDOOR UNIT POWER WIRING mm OUTDOOR UNIT POWER WIRING GROUND WIRING STRONG ELECTRIC SIGNAL WEAK ELECTRIC SIGNAL INDOOR OUDOOR CONNECTING WIRING mm 16K 1 Phase 220 240V 50Hz 60Hz 20 16 3x1 5 4x...

Страница 37: ...nutes or until the Compound Meter reads 76cmHG 105 Pa 2 3 4 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no ch...

Страница 38: ...ndard pipe length x60g 0 64oZ m ft Total pipe length standard pipe length x65g 0 69oZ m ft R410A orifice tube in the indoor unit Total pipe length standard pipe length x30g 0 32oZ m ft Total pipe leng...

Страница 39: ...ectly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the drainag...

Страница 40: ...fications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website...

Отзывы: