Refrigerant piping
Connection
Note on Pipe Length
When connecting refrigerant piping,
do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.
Refrigerant Piping Connection
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height
between the indoor and outdoor units meets the requirements shown in the following table :
The Maximum Length And Drop Height Based on Models. (Unit: m/ft.)
Type of model
Capacity (Btu/h)
Length of piping
Maximum drop height
North America,
Australia
and the
eu frequency
conversion Split
Type
<15K
25/82
10/32.8
≥
15K - <24K
30/98.4
20/65.6
≥
24K - <36K
50/164
25/82
≥
36K -
≤
60K
75/246
30/98.4
Other Split Type
12K
15/49
8/26
18K-24K
25/82
15/49
30K-36K
30/98.4
20/65.6
42K-60K
50/164
30/98.4
Liquid side
Indoor
Outdoor
Liquid side
Indoor
Outdoor
X
Liquid side
Indoor
Outdoor
X
CAUTION
Mark the data plate with the Orifice installed(for some models).
Please purchase the fittings according to the requirements in the manual strictly.
Refer the diagram when installing.