M thermal Mono
72
200208
Midea
M
ther
ma
l Mo
no
Se
rvice M
an
ual
4.14
H8 Troubleshooting
Digital display output
4.14.1
Description
4.14.2
Pressure sensor error.
Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user
interface.
Possible causes
4.14.3
Pressure sensor not connected properly or has malfunctioned.
Refrigerant system main PCB damaged.
Procedure
4.14.4
H8
No
High pressure sensor connection on
refrigerant system main PCB is loose
Yes
Ensure the sensor is connected properly
No
High pressure sensor has short-circuited
or failed
1
Yes
Replace the sensor
No
Replace refrigerant system main PCB
Notes:
1. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor
has failed. The pressure sensor connection on each type of refrigerant system main PCB is labelled in Figures 4-2.2, 4-2.4 and 4-2.6 in Part 4, 2.3 “Main
PCBs for Refrigerant System, Inverter Modules and Filter Boards”. Refer also to Part 2, 1 “Layout of Functional Components”.
Midea CAC Confidential
Mono
Содержание 06RY1
Страница 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Страница 2: ...Mono...
Страница 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Страница 113: ...Mono...
Страница 114: ...kaisai com...