E3 / E4 / H2 / H3 / Ed / HA / H5 / H9/ Eb
/ E7 / EC
Temperature sensor connection on
hydronic system main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed
2
Yes
Replace the sensor
No
Replace hydronic system main PCB
Notes:
1. Backup electric heater water outlet temperature sensor,
water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor, water side heat
exchanger refrigerant outlet (gas pipe) temperature sensor, water side heat exchanger water inlet temperature sensor and water side heat exchanger
water outlet temperature sensor connections are port CN6 on the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for
Hydronic System”). Domestic hot water tank temperature sensor connection is port CN13 on the hydronic system main PCB (labeled 9 in Figure 4-2.1 in
Part 4, 2.2 “Main PCB for Hydronic System”). Circuit 2 water outlet temperature sensor connection is port CN15 on the hydronic system main PCB (labeled
10 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic System”). Room thermostat connection is port CN3 on the hydronic system main PCB (labeled 28 in
Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic System”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 4-5.1 or 4-5.3 in Part 4, 5.1 “Temperature Sensor Resistance Characteristics”.
Midea CAC Confidential
M thermal Mono
202008
61
4.6
E5, E6, E9, EA Troubleshooting
Digital display output
4.6.1
Description
4.6.2
E5 indicates an air side heat exchanger refrigerant outlet temperature sensor error.
E6 indicates an outdoor ambient temperature sensor error.
E9 indicates a suction pipe temperature sensor error.
EA indicates a discharge temperature sensor error.
Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user
interface.
Possible causes
4.6.3
Temperature sensor not connected properly or has malfunctioned.
Damaged refrigerant system main PCB.
Midea CAC Confidential
Mono
Содержание 06RY1
Страница 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Страница 2: ...Mono...
Страница 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Страница 113: ...Mono...
Страница 114: ...kaisai com...