H7 Troubleshooting
Digital display output
4.13.1
Description
4.13.2
Abnormal main circuit voltage.
Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user
interface.
Possible causes
4.13.3
Power supply voltage not within ±10% of rated voltage or a phase is missing.
Outdoor unit powered on immediately after being powered off.
Loosened wiring within electric control box.
High voltage circuit error.
Main PCB damaged.
Midea CAC Confidential
M thermal Mono
202008
71
Procedure
4.13.4
H7
Power supply voltage is not within ±10%
of rated voltage or a (on 3-phase models)
phase is missing
Yes
Provide normal power supply
No
Wires between refrigerant system main
PCB, AC filter board (on 3-phase models)
and electric control box power supply
terminals are loose
Yes
Ensure the wires are connected properly
No
Outdoor unit powered on immediately
after being powered off
Yes
Power-off the unit and wait for at least 3
minutes before powering-on
No
High voltage circuit error has occurred,
such as the compressor has
malfunctioned, the fan motor has
short-circuited, or the inverter module
has short-circuited
Yes
Replace or repair the relevant parts
No
Replace refrigerant system main PCB
Midea CAC Confidential
Mono
Содержание 06RY1
Страница 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Страница 2: ...Mono...
Страница 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Страница 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Страница 113: ...Mono...
Страница 114: ...kaisai com...