Undercounter Refrigerators and Freezers
PAGE 7
5. clEAnInG tHE condEnsER/FIltER
The most important thing you can do to insure a long, reliable service life for your Kairak
is to regularly clean the condenser coil and or filter if provided.
The microprocessor control will notify you through a “CLN-FIL” message when the
condensing temperature of the refrigerator reaches 140 degrees F or greater. If the
condensing temperature reaches 160 degrees F the compressor will automatically turn
off . When the temperature drops below 140 degrees F the compressor will restart and
when the temperature drops below 120 degrees F the alarm will reset.
WARnInG: dIsconnEct ElEctRIcAl PoWER sUPPlY BEFoRE clEAnInG AnY
PARts oF tHE UnIt.
To clean the condenser/filter, first disconnect electrical power to the cabinet and remove
the front louver assembly. To do so, place hands under the louver panel and pull out and
up to get louver panel off bracket of the unit (Figure 3).
Proceed to vacuum or brush any dirt, lint or dust from the finned condenser coil/filter, the
compressor and other cooling system parts. If significant dirt is clogging the condenser
fins or filter, use compressed air to blow this clear. To replace the louver assembly reverse
the process.
FIGURE 3