blueplanet hybrid 10.0 TL3
Page 57
List of displayed information
Information indicates limitations of the device functions.
Code
Meaning
Explanation / recommendation
I001
Heat sink temperature
The temperature of the heat sink is too high. The power is
reduced. Check the installation.
I002
Temperature of hy-switch
The internal temperature of hy-switch is too high. Check the
installation.
I003
Battery temperature
The battery temperature is too high. The battery power is
reduced.
I010
Power reduction
The energy supplier has reduced the power of the device. Wait
until the power setting changes.
I031
I032
Deactivation by button
Device has been switched off by button.
I040
Battery charge balancing
The connected batteries have very different states of charge.
Charge balancing of the battery is recommended.
I121
Supply settings
The setting of Pav,e is lower than P_feed_in_limit. Check the
settings in the device.
I122
Supply settings
External power target is greater than Pav,e. Check settings.
I141
Communication of hy-switch
hy-switch is switched to active, but cannot be addressed.
Check the system components of hy-switch
I142
Battery communication
The battery is switched to active, but cannot be
addressed. Check the battery
I171
Safety
The initial password has not been changed. Change password.
I201
Standalone mode
Hy-switch is connected when standalone mode is activated.
Check configuration
I202
Standalone mode
AC voltage present. The inverter does not build up a standalone
grid. Check the installation.
I203
Standalone mode
Battery cannot be discharged. The inverter does not build up a
standalone grid.
I204
Standalone mode
Battery is discharged. The inverter shuts down.
I401
Standby power function
Battery state of charge too low (below 10%). The inverter
does not build up a standby power grid
I901
Reset
The device restarts after a software update.
I902
Battery configuration
The device performs the detection of the connected battery.
Wait until the battery is detected. If persistent, check
connection.
I903
Commissioning
Device has not yet been commissioned or sufficiently
configured. Perform the commissioning procedure.
I904
FRT undervoltage
FRT undervoltage detected Wait until the result is no longer
present. If it persists, check the installation.
I905
FRT overvoltage
FRT overvoltage detected Wait until the result is no longer
present. If it persists, check the installation.