I141

 

Communication of hy-switch

 

hy-switch is switched to active, but cannot be addressed. 

Check the system components of hy-switch

 

I142

 

Battery communication

 

The battery is switched to active, but cannot be ad-

dressed. Check the battery

 

I903

 

Commissioning

 

Device has not yet been commissioned or sufficiently 
configured. Perform the commissioning procedure.

 

I904

 

FRT undervoltage

 

FRT undervoltage detected Wait until the result is no 

longer present. If it persists, check the installation.

 

I905

 

FRT overvoltage

 

FRT overvoltage detected Wait until the result is no 

longer present. If it persists, check the installation.

 

I906

 

Power reduction  
Overfrequency

 

Power reference due to overfrequency. Wait until the re-
sult is no longer present.

 

I907

 

Power reduction  

Underfrequency

 

Power reference due to underfrequency. Wait until the 

result is no longer present.

 

I908

 

Unsaved settings

 

New settings have been made on the device, but have 

not yet been saved. If necessary, the settings can be 

saved under 

User Settings

.

 

I909

 

AC overvoltage

 

AC overvoltage detected. Wait until the result is no 

longer present. If it persists, check the installation.

 

I911

 

hy-switch connection

 

Unstable connection to hy-switch. Check the installation.

 

 

9.4

 

Other faults 

 
Fault pattern: 

Display without function and device cannot be switched on 

Possible solutions: 

 

The device runs without battery power and is shut down at night. 

It starts automatically the next day. 

 

The device runs without battery power and the power supply from the PV modules is interrupted. Check the 

position of the DC disconnector and the fuse protection of the supply line. Contact your installer.  

 

The device has a power supply fault. Check the power supply and functioning of the battery. Contact your in-

staller. 

 
 
 

 

Содержание blueplanet hybrid 10.0 TL3

Страница 1: ...anslation of German original Important safety instructions These instructions form part of the product and must be carefully read observed and stored in a place which is freely accessible at all times...

Страница 2: ...wnload the current warranty conditions on the Internet at http www kaco newenergy com Definitions on product designations In these operating instructions the product blueplanet hybrid 10 0 TL3 is refe...

Страница 3: ...Integration diagram 10 3 4 Compatible accessories 11 3 4 1 KACO blueplanet hy switch 11 3 4 2 Released battery storage units 11 4 Technical data 12 4 1 General data 12 4 2 Detailed technical data 12 4...

Страница 4: ...display 37 8 3 2 Operating display 38 8 3 3 Selection menu 40 8 3 4 Deactivation in grid parallel operation 43 8 3 5 Warning fault 44 8 3 6 Warning display 45 8 4 Update 45 9 Maintenance and troublesh...

Страница 5: ...eclaration of Conformity Country specific certificates Certification for specific subassembly Certificates Storing the documents These instructions and other documents must be stored near the system a...

Страница 6: ...that is important for a specific topic or objective but that is not safety relevant 1 2 4 Symbols for instructions Prerequisite for use 1 Carry out the next step 1 Additional action sequence Interim...

Страница 7: ...aic PV power supply systems is observed Ensure operational safety by providing proper grounding conductor dimensioning and appropriate protection against short circuiting Observe all safety instructio...

Страница 8: ...ly attached to the product Any other or additional use of the device shall be regarded as improper This includes Use of a distribution system that is not described grid type Use of sources other than...

Страница 9: ...nsumption optimisation with load compensation Self Consumption If the photovoltaic system supplies energy priority is given to connected loads If the photovoltaic system has a surplus of energy the en...

Страница 10: ...nec tion Inverter fuse protection line protection The circuit breaker is an overcurrent protection device Power supply company counter The feed in counter and reference counter are to be speci fied an...

Страница 11: ...rs up to 50A 3 x 3 5mm jack connector for expandability with external current sensors up to 100A RJ45 connector for communication between KACO blueplanet hy switch and the device Fig 2 KACO blueplanet...

Страница 12: ...et hybrid 10 0 TL3 3 phase 10 kW hybrid inverter 2 integrated MPP trackers Fast load regulation 100 ms High efficiency PV grid 98 PV battery 97 Battery grid 97 Pure sinusoidal output voltage Operation...

Страница 13: ...current 0 Output levels Initial short circuit alternating current Ik first single period effec tive value 16 4 A Inrush current 1 7 A 4 3 Environmental data Table 1 Environmental data Installation he...

Страница 14: ...anual Check the equipment included 1 Carefully inspect the device for transport damage check the scope of supply 2 Immediately notify the shipping company in case of the following Damage to the packag...

Страница 15: ...ding cardboard box Packaging size 720 x 685 x 320 mm Total weight including packaging 40Kg 5 3 Installation tool The codes given in the table below are used in all usage instructions for assembly inst...

Страница 16: ...A Cable diameter 5 8 mm 5 8 mm NOTE Observe the manufacturer s instructions of the manufacturer of the connector To use the provided SUNCLIX connectors use only solar cables with a nominal cross secti...

Страница 17: ...n at the installation location Immediately remove dirt especially on vents Failure to observe these warnings may lead to device damage which is not covered by the manufac turer warranty NOTE Access by...

Страница 18: ...e careful not to damage the device when using sharp objects 3 Remove installation material and documentation 4 Reach through the housing and slide the device out of the carton 5 Remove the protective...

Страница 19: ...not mount two devices one above the other The devices may only be mounted side by side When mounted one above the other the warm air escap ing from the lower device can impair the function of the uppe...

Страница 20: ...properly it can tilt and result in a fall Always lift the device vertically Use a climbing aid for the chosen installation height Wear protective gloves and safety shoes when lifting and lowering the...

Страница 21: ...left and right side 2 After attaching the device to the wall bracket screw in the countersunk screw T_TX20 1 5 Nm on both sides to fix it Make sure that the bottom of the housing can not be moved forw...

Страница 22: ...e externally accessible The device must be mounted in a fixed position before being connected electrically Comply with all safety regulations and current technical connection specifications of the res...

Страница 23: ...t a connector from a live cable during operation WARNING To prevent the risk of fire Never cover the device completely or partially when it is in operation NOTE Opening of the device No opening is req...

Страница 24: ...component If additional residual current devices RCD and re sidual current monitors RCM are used to protect against direct or indirect contact only RCD or RCM type B are permitted on the supply side o...

Страница 25: ...e permissible bending radii during installation as the protection rating is endangered by exces sive bending forces Fig 19 Connecting the connector Fig 20 Minimum bending radius Intercept mechanical l...

Страница 26: ...0 mm 5 Then shorten wires N and L1 L2 L3 by 8 mm 6 Strip the wires by 12 mm 7 With flexible wires we recommend the use of wire sleeves conforming to DIN 46228 that are pressed together using crimping...

Страница 27: ...rve the required minimum bending radii when laying the cable Fig 19 Connecting the connector Fig 20 Minimum bending radius CAUTION Plug in or disconnect connectors Never connect or disconnect the conn...

Страница 28: ...in accordance with the technical data Observe limit values in accordance with the technical data CAUTION Grounding the PV system To ensure proper installation of the PV generator the PV module frames...

Страница 29: ...in parallel The maximum permissible nominal current DC is doubled In this way it is possible to connect several strings in parallel They must have the same voltage Un1 Un2 Unm The number of modules p...

Страница 30: ...rrent in any of the DC cables using a clip on ammeter Photovoltaic modules supply a DC voltage as soon as they are exposed to light Stripped and voltage free solar cables Whilst stripping wires ensure...

Страница 31: ...n the insulation Do not touch the exposed ends of the cables Avoid short circuits Do not connect any strings with a ground fault to the device CAUTION Damage to the PV generator in case of faulty conf...

Страница 32: ...erious injury or death due to the use of unsuitable not intrinsically safe or defective battery storage units Check the certification and release of the battery storage unit Check the battery storage...

Страница 33: ...the DC connector polarity causes equipment damage in the DC connection if it is connected permanently Please check polarity of the DC connector before connecting the battery storage unit The connecto...

Страница 34: ...ss to the public power grid DANGER Improper installation of KACO blueplanet hy switch allows components and cables to come into contact with life threatening voltages Severe injuries and or death may...

Страница 35: ...age of the public grid corresponds to the nominal value 4 Make sure the AC cable is correctly connected to the grid 5 Check the cabling of the PV modules If the points are in order the device can be s...

Страница 36: ...st version of the blueplanet hy sys software 1 Observe the separate functional description of the blueplanet hy switch software 2 Update the firmware of the device and its components Please observe th...

Страница 37: ...have sufficient voltage for the start and the grid must be connected The display is divided into two areas The current status extended measurements error messages and selection menu are displayed in t...

Страница 38: ...rid No energy transfer Energy is taken from the grid The power delivered to the grid is equal to the current power on the solar generator PL1 PL2 PL3 PPV After blueplanet hy switch has been connected...

Страница 39: ...a battery symbol with information appears on the display SOC state of charge battery voltage and operation mode charge wait discharge The battery is discharged to cover the increased household consump...

Страница 40: ...ou can jump to the next selection by briefly pressing the Set button To select and activate a menu press and hold the Set button for about 2 seconds The selection menu is exited with the back symbol E...

Страница 41: ...urns you to the higher level menu Fig 45 Exit 8 3 3 1 hy switch The hy switch determines the power consumption of the house Before use hy switch must be configured Selection of hy switch Fig 46 hy swi...

Страница 42: ...ched on or off When the battery is connected a one time search process is performed in which the battery type is automatically detected The search procedure can take a few minutes Connecting the batte...

Страница 43: ...and holding the Set button longer than 5 seconds The batteries are disconnected from the system Fig 51 Progress bar during shutdown After the device has been shut down the PV switch must be set to th...

Страница 44: ...ee messages can be displayed simultaneously Display of warning messages fault messages on the display Fig 53 Faults and warnings on the display The warning messages fault messages are listed in chapte...

Страница 45: ...device is restarted after the update requiring sufficient PV power for this purpose CAUTION No PV power If no PV power is available deactivating the battery can cause the device to shut down completel...

Страница 46: ...s up to 5 minutes NOTE Opening the device is not permitted as this will invalidate the warranty Do not attempt to eliminate faults that are not described here in chapter Warning messages fault mes sag...

Страница 47: ...cleaning agents If the device is contaminated only clean the housing cooling fins housing cover display and the LEDs with water and a cloth NOTE Refer to our service and guarantee conditions on our h...

Страница 48: ...g which is used for island formation detection If the three phase grid conditions do not correspond to the limit values entered the device switches off A005 Grid voltage Linked overvoltage The device...

Страница 49: ...grid voltage Connection to the grid is only permitted if the grid is stable otherwise an additional grid supply can increase grid instability For this reason the device checks the stability of the gri...

Страница 50: ...ck supply settings Check the Pav e and P_feed_in_limit settings The fault will occur if P_feed_in_limit is Pav e A131 Power limitation The device limits the output power as the device is too warm A132...

Страница 51: ...e Switch off the battery and check the voltage at the battery connections A high input voltage can damage the device if the fault is present for a longer period of time May also occur when the battery...

Страница 52: ...ce cannot be read from EEPROM Inform the service technician in case of repeated faults E220 Self test Initialisation error Inform the service technician in case of repeated faults E230 General fault I...

Страница 53: ...n Underfrequency Power reference due to underfrequency Wait until the result is no longer present I908 Unsaved settings New settings have been made on the device but have not yet been saved If necessa...

Страница 54: ...still present at the DC connector BAT Severe injury or death will result if the live connections are touched Only touch the PV generator cables on the insulation Do not touch the exposed ends of the c...

Страница 55: ...are externally accessible Lethal voltages are still present in the connections and cables terminals of the device even after the de vice has been switched off and disconnected Severe injuries and or d...

Страница 56: ...nnectors may be unplugged under voltage but never under load 1 Use a screwdriver S_3 0 to push out the latch on the coupling 2 Leave the screwdriver in place 3 Disconnect the DC connector from the DC...

Страница 57: ...30 3 Disengage it from the wall bracket at the top Fig 62 Tilt the device 30 and disengage it from the wall bracket 10 4 Packaging the device Device has been uninstalled 1 If possible always pack the...

Страница 58: ...If you need help solving a technical problem with one of our KACO products please contact our service hotline Please have the following information ready so that we can help you quickly and efficient...

Страница 59: ...state at the time of printing Subject to technical changes No lia bility for printing errors Werner von Siemens Allee 1 74172 Neckarsulm Germany Phone 49 7132 3818 0 Fax 49 7132 3818 703 info kaco ne...