NOTE
Observe the requirements for the communication cable
The communication cable must comply with the requirements described in 6.1, Especially in the case of
longer cable lengths, high-quality communication cables and connectors must be used to ensure that the
signal quality is adequate.
›
KACO blueplanet hy-switch is also powered by the device via the communication cable.
8
Commissioning
8.1
Hardware commissioning
WARNING
Risk of electric shock
Before connecting or checking the DC cable (PV), make sure that the DC switch is in the OFF
position.
›
Before connecting or checking the AC cable, make sure that the corresponding
circuit breaker is switched off!
1.
Check the following points before commissioning:
1.
The device must be safely and firmly mounted.
2.
Make sure the no-load voltage of the PV system meets the requirements.
3.
Make sure the no-load voltage of the public grid corresponds to the nominal value.
4.
Make sure the AC cable is correctly connected to the grid.
5.
Check the cabling of the PV modules.
»
If the points are in order, the device can be started.
2.
Starting the device
1.
Switch on the public grid at the external, AC-side disconnector mechanism.
2.
Make sure the battery storage unit is ready for operation and switch it on.
3.
Switch on the PV system with the DC isolator switch:
Turn the DC isolator switch to the "I" position.
»
Now that the device is ready for operation, it will start operating as soon as sufficient voltage is applied to the PV
input.
240 VDC is required for the start. After DC switch is turned on, the display does not come on until 60 seconds has elapsed!
If the device does not respond after 60 s when voltage is applied, the DC disconnector must be turned to the "0" position
and the polarity of the PV connections must be checked.
If warnings/errors are displayed on the LCD display, a problem or error is present. Please consult chapter 9.3 of this man-
ual for troubleshooting or contact your installer.
Authorised elec-