![Kaco blueplanet hybrid 10.0 TL3 Скачать руководство пользователя страница 34](http://html2.mh-extra.com/html/kaco/blueplanet-hybrid-10-0-tl3/blueplanet-hybrid-10-0-tl3_operating-instructions-manual_3472024034.webp)
EN
blueplanet hybrid 10.0 TL3
Page 34
Connecting the battery storage unit
DC plug connector
1.
Connect the DC connectors to the DC positive and DC negative
connectors in pairs. The connection is marked as BAT.
»
The device is connected to the battery storage unit on the DC side.
Fig. 29: BAT connection (DC)
Communication cable
1.
The communication cable of the battery is connected to the device.
The communication cable must have an RJ45 connector. It must be
connected to the BMS connection of the three communication ports
on the bottom of the device.
»
The device is communicatively connected to the battery storage unit.
Fig. 30: BMS communication connec-
tion
7.6
Connecting KACO blueplanet hy-switch to the device
KACO blueplanet hy-switch is required for the adjustment and disconnection of the grid connection or the installation
string to be compensated. This component is not required for installations without access to the public power grid.
DANGER
Improper installation of KACO blueplanet hy-switch allows components and cables to come into contact
with life-threatening voltages
Severe injuries and/or death may occur if the cables and terminals are touched.
›
Observe the KACO blueplanet hy-switch manual.
›
The device must be mounted in a fixed position before being connected electrically.
›
The device is only permitted to be installed by an authorised electrician.
›
Switch off the grid voltage by turning off the external circuit breakers.
›
Check that all AC and DC cables are completely free of current using a clip-on ammeter.
KACO blueplanet hy-switch must be installed according to the enclosed manual.
Connecting KACO blueplanet hy-switch
1.
Connect the communication cable of KACO blueplanet hy-switch to
the device. The communication cable must have an RJ45 connector on
both sides. It must be connected to the hy-switch connection of the
three communication ports on the bottom of the device.
»
The device is connected to Kaco blueplanet hy-switch.
Fig. 31: Connecting the KACO blue-
planet hy-switch communication
Authorised elec-