0639-990-21---30j_2010.07.indd
SLA
0639-990/22j
Page 37 of 46
Operating instructions
9
SHuT-DOWN
no particular measures need to be taken for de-commissioning the installation.
if the sliding door installation will not be used during at least 1 month, it is re-commended
to pull out the mains plug (and, if provided, the battery plug).
Attention:
for this purpose, the door must be in the operating mode niGhT, in order to
avoid a discharge of the emergency battery (option).
if an installation with emergency battery is planned to be taken out of operation for a
period exceeding 1 year, the mains cable of insttalations containing an emergency battery
must be plugged in once a year for at least 24 hours in order to allow the batterie to be
recharged.
for taking the installation back into operation, all you have to do is to plug in the mains
cable/the battery connector and select the operating mode on the key-operated program
switch.
Attention:
if the installation is re-commissioned at low temperatures, it must be swit-
ched on 1...2 hours prior to the actual setting-up procedure (so that the
operating temperature can be reached).