background image

Online operation with firmware option Access Manager 

 

 

30

 

k4evo707en-2012-07 

 

4.2.2 

Electric strike operating mode 

Example: 

 

 
This operating mode is particularly associated with doors which have electrical locking elements 
(electric strike, magnet). 
Triggered by an authorized booking, door opener key, or door handle, the Access 
authorized/Access allowed signal is generated.  
Only now is the electric strike triggered. From this point onwards, the door is enabled for opening 
and the set operation time for the relay starts running. If the door is opened, monitoring of the  
pre-alarm and alarm times (Door open too long) starts running. 
 

 

 

 

Examples of other door configurations with the associated time-based diagrams are provided in the 
relevant system documentation and/or in the online help. 
 
 
 

4.2.3 System 

requirements 

Details can be found in the relevant documentation, e.g., Release Overview, Release Notes. 
 
 

Содержание MIFARE

Страница 1: ...Compact Reader MIFARE Compact Reader LEGIC Technical Manual Doc No k4evo707en 2012 07...

Страница 2: ...1 www kaba ch Kaba GmbH Access Workforce Management Albertistrasse 3 D 78056 Villingen Schwenningen Germany Phone 49 7720 603 0 www kaba de This document must not be reproduced in any way or used in a...

Страница 3: ...ng distances with Compact Reader MIFARE 15 2 4 5 Typical maximum reading distances with Compact Reader LEGIC 15 2 4 6 Reading and writing distance in the case of direct mounting on metal surfaces 15 2...

Страница 4: ...izing online 36 4 8 4 Putting the Compact Reader into operation 36 4 9 Maintenance 37 4 9 1 Restart 37 4 9 2 Factory reset 37 4 9 3 Firmware LEGIC OS update 38 4 9 4 Cross upgrade 40 5 Online operatio...

Страница 5: ...1 Topology 61 7 2 Functionalities with firmware option E300 V4 62 7 2 1 Operation as validation actuator 63 7 2 2 Electric strike operating mode 63 7 3 MIFARE LEGIC module 65 7 3 1 Supported RFID tec...

Страница 6: ...79 9 1 2 The Compact Reader does not read correctly 79 9 2 During operation 79 9 2 1 The Compact Reader is not or is only temporarily recognized by the host system 79 9 2 2 The Compact Reader does not...

Страница 7: ...ensure that the product is used correctly and safely The Compact Readers MIFARE LEGIC are used in a wide range of Kaba system solutions The only differences are the particular firmware options for th...

Страница 8: ...B RCC RCE Compact Reader with firmware option E300 V4 or N T U300 V3 Compact Reader with firmware option Access Manager Compact Reader with firmware option Subterminal Compact Reader with firmware opt...

Страница 9: ...a their own account other users via the following guest account Customer number leave blank User name docu2010de kbs kaba com Password k5s 7smq Kaba Portal AC 1 5 Document availability All documents a...

Страница 10: ...al Factory reset INI reset with firmware option E300 V4 or N T U300 V3 Cold start with firmware option Subterminal Remote reader Remote Reader MIFARE RR M or Remote Reader LEGIC RR L Access manager Ac...

Страница 11: ...ay elements signal both the operating state and access decision visually as well as acoustically Thanks to the new quickwire technology installation is quick and easy The device is wired to the mounti...

Страница 12: ...Firmware option Access Manager Firmware option Subterminal Firmware option E300 V4 Firmware option N T U300 V3 LEGIC only CardLink 1 1 CardLink 1 0 CardLink 1 1 CardLink 1 0 Compact Reader Firmware op...

Страница 13: ...SO 15693 LEGIC RF Media applications Unique number UID X X X X X Safe UID X X X X X Card ID X X X X Kaba Group Header X X X Kaba advant ID X X LEGIC access advant X X LEGIC access pool prime X CardLin...

Страница 14: ...3 If a Compact Reader was already successfully launched with the same SAM 63 C2 it confirms immediately with a triple beep 2 3 3 2 Deleting launch data Launched data can be deleted as follows All laun...

Страница 15: ...Antenna adaptation The slide switch can be used to calibrate the antenna for mounting on metallic or non metallic bases Always put the slide switch in the Air position except when using a metallic bas...

Страница 16: ...ound 7 Door handle contact or door opener key REX IN1 8 Frame contact FC IN2 IMPORTANT Given the different use firmware options individual connections can be used for different purposes or not at all...

Страница 17: ...Terminal number Meaning 3 NC normally closed 4 COM 5 NO normally open 2 5 4 Connecting the tamper switch 6 Where necessary the external tamper monitoring function of the Compact Reader can be connect...

Страница 18: ...dividual basis in the host system DIP switches 3 and 4 are used to define the inputs 2 5 5 1 Inputs without line monitoring 2 5 5 2 Inputs with line monitoring For monitoring purposes the lines must b...

Страница 19: ...e option Subterminal and firmware option cDML For information on the RS 485 cable see Chapter 3 2 1 Page 23 and on the cabling bus termination Chapter 3 5 1 Page 25 2 5 6 1 Connecting the RS 485 inter...

Страница 20: ...0 Hz 10 34 V DC Power consumption typically 1 2 W max 2 2 W Interfaces HF RFID Integrated antenna RS 485 For connection to the parent control unit Firmware Option Access Manager KCP protocol galvanic...

Страница 21: ...ns Ambient conditions Operating temperature 25 70 Storage temperature 40 85 Relative humidity 0 95 non condensing Protection type IP54 only with rear panel sealing mat and flush cable mounting 2 6 1 D...

Страница 22: ...Use a cable loop siphon to prevent water ingress In the case of surface cable mounting spacer frame route the cable downwards or to the side create a cable feed through opening Option for rear panel...

Страница 23: ...ype J Y ST 4 x 2 x 0 6mm 4 x 2 x 0 8mm 4 x 2 x 1 0mm Max cable length 50m 100m 350m Firmware option Subterminal Cable type CAT 5 S UTP 4 x 2 x AWG 24 Cable type J Y ST 4 x 2 x 0 6mm Max cable length 2...

Страница 24: ...the C common connection at the Compact Reader and the connected devices With bus cabling for the communication connections please also ensure that there is a continuous connection between the shieldin...

Страница 25: ...re To avoid short circuits the sheath wire should be insulated with a heat shrinkable tube for example Lines A and B are routed as a twisted pair of conductors and are not transposed If multiple remot...

Страница 26: ...on connect the shieldings of the RS 485 cables between the devices to each other Max length between the last two devices is 1 200 m 3 5 1 2 Example of star cabling The terminating resistor is adjusted...

Страница 27: ...cture hardware compatibility system solutions and connections for the Compact Reader are described in the device description in Chapter 2 Page 11 You will find an overview of how this technical manual...

Страница 28: ...tion and devalidation Standalone access control without host system see also chapter 4 2 1 page 29 Restrictions if the connection is interrupted offline MIFARE Reduced authorization check based on sit...

Страница 29: ...ontrol unit Only events max 2000 are transmitted after connection with a parent control unit The time and date stamps are however no longer correct i e invalid 4 2 1 2 With MIFARE Only the site key or...

Страница 30: ...d signal is generated Only now is the electric strike triggered From this point onwards the door is enabled for opening and the set operation time for the relay starts running If the door is opened mo...

Страница 31: ...14443A MIFARE ISO 14443A LEGIC ISO 14443A LEGIC ISO 15693 LEGIC RF Media applications Unique number UID 1 X X X X Safe UID X Card ID X X X X Kaba Group Header X X X Kaba advant ID X X LEGIC access adv...

Страница 32: ...disconnected from the power supply Changes to settings are only applied after the power supply has been interrupted Disconnect the Compact Reader from the power supply before carrying out any wiring w...

Страница 33: ...thin the bus for devices in a bus cabling arrangement see also Chapter 3 5 1 1 Page 25 with 1 2 bus lines 1 ON and 2 OFF Bus termination 4 7 k star cabling Bus termination 4 7 k on each individual dev...

Страница 34: ...Compact Reader is to support simplified door management in offline mode inputs 1 and 2 need to be connected in accordance with Chapter 2 5 5 Page 18 and defined in accordance with Chapter 4 4 5 1 Page...

Страница 35: ...4 7 LED display Displays the access decision and operating state by means of the central light symbol red green and an acoustic signal transmitter buzzer Error correction tips can be found in Chapter...

Страница 36: ...e of this address It will be needed again for the configuration in the host system 2 Set the terminating resistor on the RS 485 bus in accordance with the bus topology 3 Configure inputs IN1 and IN2 c...

Страница 37: ...et to their initial values factory settings The factory reset takes around 3 s The access point is blocked for the entire time Task Illumination unit Compact Reader 1 Switch off the power supply on th...

Страница 38: ...The actual update with the service tool is described in detail in RM_Access_Manager 4 9 3 2 Firmware LEGIC OS update with Programmer 1460 Firmware updates can only be performed with the Kaba evolo Ser...

Страница 39: ...enable the programmer to be plugged into an installed reader we recommend the following course of action 1 Open the Compact Reader 2 Remove the quickwire plug with a screwdriver 3 Connect the program...

Страница 40: ...the flashing mentioned in the previous step does not take place If the programmer is removed before the power is disconnected the LEDs flash as in update mode Flashing stops 1x short beep LED briefly...

Страница 41: ...evice description in Chapter 2 Page 11 You will find an overview of how this technical manual is structured in Chapter 1 Page 7 IMPORTANT If an existing Kaba exos cDML is to be replaced with a Compact...

Страница 42: ...locking elements Support for a connected door opener key or door handle contact Monitoring of door status using frame magnetic contact External tamper monitoring PCB plugged in CardLink support valid...

Страница 43: ...nal is generated Only now is the electric strike triggered From this point onwards the door is enabled for opening and the set operation time for the relay starts running If the door is opened monitor...

Страница 44: ...e below Supported RFID technology LEGIC advant LEGIC prime Supported RFID standard LEGIC ISO 14443A LEGIC ISO 15693 LEGIC RF Media applications Unique number UID 1 X X Safe UID X Card ID X X Kaba Grou...

Страница 45: ...nnected from the power supply Changes to settings are only applied after the power supply has been interrupted Disconnect the Compact Reader from the power supply before carrying out any wiring work d...

Страница 46: ...evices in a bus cabling arrangement see also Chapter 3 5 1 1 Page 25 with 1 2 bus lines 1 ON and 2 OFF Bus termination 4 7 k star cabling Bus termination 4 7 k on each individual device see also Chapt...

Страница 47: ...s to exhibit the same behavior in both online and offline mode inputs 1 and 2 need to be connected in accordance with Chapter 2 5 5 Page 18 and defined in accordance with Chapter 5 4 5 2 Page 47 The p...

Страница 48: ...ED display Displays the access decision and operating state by means of the central light symbol red green and an acoustic signal transmitter buzzer Error correction tips can be found in Chapter 9 Pag...

Страница 49: ...address It will be needed again for the configuration in the host system 2 Set the terminating resistor on the RS 485 bus in accordance with the bus topology 3 Configure inputs IN1 and IN2 correctly...

Страница 50: ...their initial values factory settings The factory reset takes around 3 s The access point is blocked for the entire time Task Illumination unit Compact Reader 1 Switch off the power supply on the Com...

Страница 51: ...erating system for Kaba Programmer 1460 FTDI CDM supports D2XX and VCP functionality http www ftdichip com FTDrivers htm Install Microsoft Net Framework 4 Client Profile http www microsoft com net Ins...

Страница 52: ...he flashing mentioned in the previous step does not take place If the programmer is removed before the power is disconnected the LEDs flash as in update mode Flashing stops 1x short beep LED briefly f...

Страница 53: ...cides whether to open the doors for example The operator is guided by means of acoustic and visual signaling triggered by corresponding B web terminal commands The relay within the Compact Reader can...

Страница 54: ...43A MIFARE ISO 14443A LEGIC ISO 14443A LEGIC ISO 15693 LEGIC RF Media applications Unique number UID 1 X X X X Safe UID X Card ID X X X X Kaba Group Header X X X Kaba advant ID X X LEGIC access advant...

Страница 55: ...Page 16 regardless of firmware option 6 4 1 Changing the settings IMPORTANT DIP switch and slide switch settings may only be made when the equipment is disconnected from the power supply Changes to s...

Страница 56: ...ess is fixed at 00 The Compact Reader automatically detects the baud rate of the sub party line 9 600 or 19 200 default Switch 5 ON The Compact Reader is started after switch on in system mode service...

Страница 57: ...y switch 2 6 Connect the RS 485 sub party line 4 to the B web terminal 7 If required connect the door opener via the relay output 5 8 Connect the power supply 3 for the Compact Reader 6 5 Putting into...

Страница 58: ...applies to parameters which were changed via the system mode Parameters changed via LOWPAR are set to the default values by a cold start Configuration parameters are set with the SETHWC command and t...

Страница 59: ...system for Kaba Programmer 1460 FTDI CDM supports D2XX and VCP functionality http www ftdichip com FTDrivers htm Install Microsoft Net Framework 4 Client Profile http www microsoft com net Install the...

Страница 60: ...ted the flashing mentioned in the previous step does not take place If the programmer is removed before the power is disconnected the LEDs flash as in update mode Flashing stops 1x short beep LED brie...

Страница 61: ...configuration LED display putting into operation factory reset and firmware update for the Compact Reader The structure hardware compatibility system solutions and connections for the Compact Reader a...

Страница 62: ...60 No No Door individual right Up to 60 4 Up to 255 7 No Door group individual right Up to 39 4 Up to 255 7 No Reservation door individual right Up to 18 4 Up to 100 No Door group right Up to 11 4 Up...

Страница 63: ...12 07 63 7 2 1 Operation as validation actuator With LEGIC For operation as a validation actuator write authorization launch must be assigned to the Compact Reader see Chapter 2 3 3 Page14 7 2 2 Elect...

Страница 64: ...tion INI reset the s module interprets the current switch position as the output position If this position is changed the action defined under activation is performed It is possible therefore to use a...

Страница 65: ...sic LEGIC advant LEGIC prime Supported RFID standard MIFARE ISO 14443A MIFARE ISO 14443A LEGIC ISO 14443A LEGIC ISO 15693 LEGIC RF Media applications Unique number UID X X Safe UID 1 X X X X X Card ID...

Страница 66: ...may only be made when the equipment is disconnected from the power supply Changes to settings are only applied after the power supply has been interrupted Disconnect the Compact Reader from the power...

Страница 67: ...ise the rotary switch setting applies for the function The rotary switch is set to 0 on delivery default pulse mode 1 s Function 0 Software mode default 1 s 1 Pulse mode 0 5 s 2 Pulse mode 1 s 3 Pulse...

Страница 68: ...act Reader is equipped with a self learning function During initialization INI reset the Compact Reader interprets the current switch position as the output position If this position is changed the ac...

Страница 69: ...a metallic base The slide switch is set to the Air position on delivery default Position Meaning In Air position for a non metallic base default In Metal position for a metallic base 7 7 LED display...

Страница 70: ...uipment is disconnected from the power supply Changes to settings are only applied after the power supply has been interrupted Disconnect the Compact Reader from the power supply before carrying out a...

Страница 71: ...Master 7 9 2 1 INI reset with DIP switch 6 An INI reset takes around 3 seconds before the remote reader is ready for operation once more The access point is blocked for the entire time Task LED Compa...

Страница 72: ...required configuration data see Chapter Page Access point ready for bookings again 6 Remove programmer and wait for timeout to elapse State LED lights up again or flashes Green or not lit 7 9 2 3 INI...

Страница 73: ...ammer 1460 FTDI CDM supports D2XX and VCP functionality http www ftdichip com FTDrivers htm Install Microsoft Net Framework 4 Client Profile http www microsoft com net Install the Kaba evolo Service T...

Страница 74: ...ccessful Firmware LEGIC OS download 1x short beep LED briefly flashes green twice 6 Switch off the power supply at the Compact Reader set DIP switch 6 to OFF remove the programmer and reconnect the po...

Страница 75: ...s green twice 2 Present programming Master to registration unit RFID antenna actuator is now in programmer mode until the actuator times out or the programmer breaks the connection 1x short beep 3 Dow...

Страница 76: ...of authorization are stored in the remote reader This means the Compact Reader is responsible for the authorization check and access point triggering The Compact Reader with the firmware option N T U...

Страница 77: ...Pulse mode 300 s B Not in use C Not in use D Not in use E Not in use F Bistable mode 8 4 Maintenance 8 4 1 Programming with the programmer 1364 Programming through the existing V3 tool chain is compa...

Страница 78: ...and 6 has no effect Information The reader restarts every 10 s and the signaling begins again LED IN1 flashes green 2x short beeps then red green flashing flashes only with the compact reader 3 Connec...

Страница 79: ...whether the configuration of the access point has been changed in the host system 9 2 2 The Compact Reader does not read correctly Check whether the user has changed anything on the system Check whet...

Страница 80: ...rminating resistors of all the affected components must be checked following any dismantling procedure The configuration of the host system must also be checked 10 3 Disposal Before disposal the syste...

Страница 81: ...time registration RFID tags can be read without contact by the integrated antenna Access decisions and operating states are signaled visually as well as acoustically on the Compact Reader IMPORTANT T...

Страница 82: ...EC directive 1999 5 EC Radio and Telecommunications Terminal Equipment Directive R TTE To the best of our knowledge this device does not contain any materials in terms of the concentrations or applic...

Отзывы: