16
RDS-2 Specifications
•
Solenoid rated for continuous duty (with
RDS
).
•
Input voltage required: 115 VAC, 60 Hz, 5 amps to transformer.
•
Output voltages:
- First Device: Terminal #1 and #2; 24V DC impulse; 5V DC continuously after impulse.
- Second Device: One second delay after first device; Terminal #3 and #4; 24V DC impulse; 5V DC
continuously after impulse.
•
Dip switch (when on) will hold device(s) retracted for set time period as indicated below:
DIP #
1
2
3
4
5
6
Hold Time (seconds)
2
4
8
16
32
64
•
DIP switches moved to the ON position have a hold time of all ON settings added together. Example:
DIP #1 and #2 = 6 seconds hold time. A hold time of less than 4 seconds (DIP #1 only) is not
recommended.
•
For continuous ELR retraction, turn all DIP switches to OFF position and apply a jumper or other
source switch to terminal #7 and #8.
•
A green flashing LED indicates that power is applied to the board. A solid green LED indicates that
the device(s) are being retracted. An orange LED indicates that the devices are being held in the
retracted position. A flashing red LED indicates a short in the wiring between the board and device.
Operational Test for FSE (Fail Secure) Devices
1.
With power engaged, the trim will be unlocked.
2.
Function the control device or disconnect main power from the RDS-2, the trim will lock.
3.
With power disengaged, the trim will be locked. Check to ensure that the key-override feature functions
properly by unlocking the trim.