RWZ1bA14.sch
X2
FACP
Rab (10k)
3
4
RWZ1bA15.sch
Ver. 1/14 Mo
17 Mar. 2014
SHEVS Control Centre RWZ 1b
Line
Rab (10k)
X2
Rab (10k)
T
.........
.........
3
.........
L2
L1out
5
2
L1in
3
4
.........
.........
3
.........
L2
L1out
5
2
L1in
.........
.........
3
.........
L2
L1out
5
2
L1in
+
T
-
T
Line
Rab (10k)
T
+
T
-
T
or
4
A -
9
/
When connecting an FACP, remove terminating resistor
Rab from Control Centre and connect it as shown.
Fire Alarm Control Panel (FACP)
Ral
(1k5 / 0.5 W)
FACP
NO-
contact
Additionally, connect release resistor
Ral (affixed to Control Centre door
when supplied), as shown.
Automatic fire detectors or Fire Alarm Control Panel (FACP)
Colour code for resistors: 10k = brown/black/black/red 1k5 = brown/green/black/brown
When connecting fire detectors, remove
terminating resistor Rab from Control
and connect it to the last detector.
(terminals 2, 3 and 5)
or RM 3 / TM 3
(terminals L1 in, L1 out and L2)
Automatic fire detectors RM 2 / TM 2